2002-05-02 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEWS OF 3/4/02 AND 3/21/02: |
| |
| 1) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| THE SITE SPECIFIC SURVEY DRAWING IS NOT |
| APPLICABLE TO A MASTER MODEL PLAN REVIEW |
| AND MUST BE REMOVED BEFORE RESUBMITTAL. |
| |
| 2) THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED.THE GENERAL NOTES (SHEET G1) |
| STILL REFER TO A BASIC WIND SPEED OF |
| 110MPH WHICH DOES NOT COMPLY WITH 2001 |
| FLORIDA BUILDING CODE.THE STATED WIND |
| SPEED AND VELOCITY PRESSURE SHALL BE |
| AMENDED TO DEMONSTRATE COMPLIANCE. |
| |
| 3) THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED.WITH REFERENCE TO THE |
| MASONRY COLUMN ADJACENT TO THE FAMILY |
| ROOM PATIO DOOR, SHEET A-02 (FOUNDATION |
| PLAN) AND SHEET A-3 (FLOOR PLAN) ARE |
| STILL SHOWING DIFFERENT COLUMN TYPES. |
| AMEND SHEET A-02 TO RECTIFY. |
| |
| 13) FBC 1606.1.4GARAGE DOOR PRODUCT |
| APPROVAL.THE GENERAL NOTES (SHEET G1) |
| STATE THAT THE MAXIMUM POSITIVE |
| COMPONENT AND CLADDING PRESSURE = 37PSF |
| AND THE MAXIMUM NEGATIVE COMPONENT AND |
| CLADDING PRESSURE = -42PSF. THESE EXCEED |
| THE CAPACITY STATED IN THE GARAGE DOOR |
| PRODUCT APPROVAL, IN WHICH TABLE 1 AND |
| DRAWING SBC-580-015, STATE AN ALLOWABLE |
| POSITIVE TRANSVERSE WIND LOAD OF 31.9PSF |
| AND AN ALLOWABLE NEGATIVE TRANSVERSE |
| WIND LOAD OF -36.8PSF.THE GARAGE DOOR |
| WIND LOAD CAPACITY MUST EXCEED THE |
| STATED CLADDING AND COMPONENT PRESSURE. |
| RE-SPECIFY TO DEMONSTRATE COMPLIANCE. |
| |
| 14) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| THE SUBMITTED PRODUCT APPROVAL NOTICE OF |
| ACCEPTANCE NO. 00-0307.04 IS STILL |
| MISSING DRAWING SHEETS 1 THROUGH 15 |
| (INCLUDING SHEET 10A). |
| |
| |
| NOTE: |
| CHAPTER 553.80(2)(B) FLORIDA STATUTES |
| STATES THAT A LOCAL GOVERNMENT SHALL |
| IMPOSE A FEE OF FOUR TIMES THE FEE FOR |
| PLAN REVIEW, IF PLANS ARE REJECTED THREE |
| OR MORE TIMES FOR REPEATED FAILURE TO |
| CORRECT A CODE VIOLATION. |
| |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| ROBERT BROWN(561) 659 8096 EXT 8499 |