2002-05-02 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEWS OF 3/4/02 AND 3/21/02:
  
 1) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE SITE SPECIFIC SURVEY DRAWING IS NOT
 APPLICABLE TO A MASTER MODEL PLAN REVIEW
 AND MUST BE REMOVED BEFORE RESUBMITTAL.
  
 2) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE GENERAL NOTES (SHEET G1)
 STILL REFER TO A BASIC WIND SPEED OF
 110MPH WHICH DOES NOT COMPLY WITH 2001
 FLORIDA BUILDING CODE.THE STATED WIND
 SPEED AND VELOCITY PRESSURE SHALL BE
 AMENDED TO DEMONSTRATE COMPLIANCE.
  
 3) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.WITH REFERENCE TO THE
 MASONRY COLUMN ADJACENT TO THE FAMILY
 ROOM PATIO DOOR, SHEET A-02 (FOUNDATION
 PLAN) AND SHEET A-3 (FLOOR PLAN) ARE
 STILL SHOWING DIFFERENT COLUMN TYPES.
 AMEND SHEET A-02 TO RECTIFY.
  
 13) FBC 1606.1.4GARAGE DOOR PRODUCT
 APPROVAL.THE GENERAL NOTES (SHEET G1)
 STATE THAT THE MAXIMUM POSITIVE
 COMPONENT AND CLADDING PRESSURE = 37PSF
 AND THE MAXIMUM NEGATIVE COMPONENT AND
 CLADDING PRESSURE = -42PSF. THESE EXCEED
 THE CAPACITY STATED IN THE GARAGE DOOR
 PRODUCT APPROVAL, IN WHICH TABLE 1 AND
 DRAWING SBC-580-015, STATE AN ALLOWABLE
 POSITIVE TRANSVERSE WIND LOAD OF 31.9PSF
 AND AN ALLOWABLE NEGATIVE TRANSVERSE
 WIND LOAD OF -36.8PSF.THE GARAGE DOOR
 WIND LOAD CAPACITY MUST EXCEED THE
 STATED CLADDING AND COMPONENT PRESSURE.
 RE-SPECIFY TO DEMONSTRATE COMPLIANCE.
  
 14) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE SUBMITTED PRODUCT APPROVAL NOTICE OF
 ACCEPTANCE NO. 00-0307.04 IS STILL
 MISSING DRAWING SHEETS 1 THROUGH 15
 (INCLUDING SHEET 10A).
  
  
 NOTE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499