2002-04-18 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE, LOAD CALCUALTIONS
 STILL DO NOT CORRELATE WITH NEC ART 220.
  
 2)NOTE: PLEASE NOTE THAT POOL PANEL IS
 SHOWN ON PANEL SCHEDULE AS 1-POLE 20A
 W/ #12. PLEASE NOTE ON RISER AS 30A W/
 #6 AWG. STILL NO NEUTRAL FOR POOL LIGHT?
  
 3)NOTE: PLEASE NOTE THAT POOL PUMP IS
 SHOWN COMING FROM PANEL IN GARAGE ALSO??
 PLEASE CLARIFY IF POOL PANEL IS EVEN
 NEEDED IF EQUIPMENT IS GOING TO BE FED
 FROM MAIN PANEL.
  
 4)NOTE: PLEASE NOTE 5KW DRYER SHOWN AS
 1-POLE 20A W/#12 AWG???
  
 5)NOTE: PLEASE NOTE THAT CODE FOR
 KITCHEN OUTLETS IN NOTES IS STILL REF.
 WRONG ART. PLEASE ALSO NOTE MISSING
 OUTLET ON KITCHEN COUNTERSPACE PER
 210-52C. THE ART REF FOR KITCHEN IS THE
 ART FOR BATHS??
  
 6)NOTE: PLEASE NOTE THAT THE ARC FAULT
 PROETCTION FOR BEDROOMS IS STILL NOT
 LISTED ON PANEL SCHEDULE. 210-12
  
 7)NOTE: PLEASE NOTE THAT RISER IS SHOW-
 -ING 3/0`S FOR 150A SERVICE. PLEASE NOTE
 THAT IF 3/0` ARE SHOWN ON PLANS, THEN
 THEY WILL BE REQ`D TO BE INSTALLED. THIS
 IS JUST A NOTE. 3/0`S CAN STILL BE USED
 IF SO DESIRED.
  
  
  
 ********* NOTE ********** NOTE*******
 PLEASE NOTE THAT THIS IS THE 3RD TIME
 THE PLANS HAVE BEEN REVIEWED FOR THIS
 MODEL. PLEASE NOTE THAT UNDER THE FLA
 ADMINISTRATIVE CODE SEC.553-80. PLANS
 REVIEW/DENIED FOR THE SAME ITEMS FOR 3
 OR MORE TIMES ARE SUBJECT TO 4X THE FEE
 FOR PLAN REVIEW.
 PLEASE NOTE THAT ALL ITEMS NEED TO BE
 ADDRESSED.
 ****************************************
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372