2002-04-18 00:00:00 | ****************** UNSAT *************** |
| |
| 1)NOTE: PLEASE NOTE, LOAD CALCUALTIONS |
| STILL DO NOT CORRELATE WITH NEC ART 220. |
| |
| 2)NOTE: PLEASE NOTE THAT POOL PANEL IS |
| SHOWN ON PANEL SCHEDULE AS 1-POLE 20A |
| W/ #12. PLEASE NOTE ON RISER AS 30A W/ |
| #6 AWG. STILL NO NEUTRAL FOR POOL LIGHT? |
| |
| 3)NOTE: PLEASE NOTE THAT POOL PUMP IS |
| SHOWN COMING FROM PANEL IN GARAGE ALSO?? |
| PLEASE CLARIFY IF POOL PANEL IS EVEN |
| NEEDED IF EQUIPMENT IS GOING TO BE FED |
| FROM MAIN PANEL. |
| |
| 4)NOTE: PLEASE NOTE 5KW DRYER SHOWN AS |
| 1-POLE 20A W/#12 AWG??? |
| |
| 5)NOTE: PLEASE NOTE THAT CODE FOR |
| KITCHEN OUTLETS IN NOTES IS STILL REF. |
| WRONG ART. PLEASE ALSO NOTE MISSING |
| OUTLET ON KITCHEN COUNTERSPACE PER |
| 210-52C. THE ART REF FOR KITCHEN IS THE |
| ART FOR BATHS?? |
| |
| 6)NOTE: PLEASE NOTE THAT THE ARC FAULT |
| PROETCTION FOR BEDROOMS IS STILL NOT |
| LISTED ON PANEL SCHEDULE. 210-12 |
| |
| 7)NOTE: PLEASE NOTE THAT RISER IS SHOW- |
| -ING 3/0`S FOR 150A SERVICE. PLEASE NOTE |
| THAT IF 3/0` ARE SHOWN ON PLANS, THEN |
| THEY WILL BE REQ`D TO BE INSTALLED. THIS |
| IS JUST A NOTE. 3/0`S CAN STILL BE USED |
| IF SO DESIRED. |
| |
| |
| |
| ********* NOTE ********** NOTE******* |
| PLEASE NOTE THAT THIS IS THE 3RD TIME |
| THE PLANS HAVE BEEN REVIEWED FOR THIS |
| MODEL. PLEASE NOTE THAT UNDER THE FLA |
| ADMINISTRATIVE CODE SEC.553-80. PLANS |
| REVIEW/DENIED FOR THE SAME ITEMS FOR 3 |
| OR MORE TIMES ARE SUBJECT TO 4X THE FEE |
| FOR PLAN REVIEW. |
| PLEASE NOTE THAT ALL ITEMS NEED TO BE |
| ADDRESSED. |
| **************************************** |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |