2002-03-21 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 3/04/02: |
| |
| 1) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| THE SITE SPECIFIC SURVEY DRAWING IS NOT |
| APPLICABLE TO A MASTER MODEL PLAN REVIEW |
| AND MUST BE REMOVED. |
| |
| 2) THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED.THE GENERAL NOTES (SHEET G1) |
| AND ROOF FRAMING NOTES (SHEET A-05) |
| STILL REFER TO A BASIC WIND SPEED OF |
| 110MPH WHICH, UNDER THE 1997 STANDARD |
| BUILDING CODE, IS BASED ON THE 'FASTEST |
| MILE'. UNDER 2001 FLORIDA BUILDING CODE, |
| THE BASIC WIND SPEED FOR THE CITY IS |
| 140MPH, BASED ON A 3 SECOND GUST.AS A |
| RESULT OF THIS REVISED METHOD OF |
| ASSESSING WIND LOAD, THE BASIC VELOCITY |
| PRESSURES WILL CHANGE.AMEND THE NOTES |
| TO REFLECT THIS. |
| |
| 3) THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED IN RESPECT OF THE MASONRY |
| COLUMNS ON EACH SIDE OF THE PATIO DOOR |
| FROM THE LIVING ROOM.SHEET A-02, |
| FOUNDATION PLAN AND SHEET A-03, FLOOR |
| PLAN ARE STILL SHOWING DIFFERENT COLUMN |
| TYPES.AMEND SHEET A-03 TO RECTIFY. |
| |
| 12) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| ADD A NOTE TO THE PLANS TO STATE THE |
| REQUIREMENT FOR HURRICANE IMPACT |
| SHUTTERS. |
| |
| 13) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| SUBMIT A PRODUCT APPROVAL FOR THE |
| GARAGE DOOR. |
| |
| 14) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| THE DRAWING SHEETS 1 THROUGH 15 WHICH |
| SHOULD ACCOMPANY THE GARAGE DOOR PRODUCT |
| APPROVAL ARE STILL MISSING. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |