2002-03-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 3/04/02:
  
 1) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE SITE SPECIFIC SURVEY DRAWING IS NOT
 APPLICABLE TO A MASTER MODEL PLAN REVIEW
 AND MUST BE REMOVED.
  
 2) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE GENERAL NOTES (SHEET G1)
 AND ROOF FRAMING NOTES (SHEET A-05)
 STILL REFER TO A BASIC WIND SPEED OF
 110MPH WHICH, UNDER THE 1997 STANDARD
 BUILDING CODE, IS BASED ON THE 'FASTEST
 MILE'. UNDER 2001 FLORIDA BUILDING CODE,
 THE BASIC WIND SPEED FOR THE CITY IS
 140MPH, BASED ON A 3 SECOND GUST.AS A
 RESULT OF THIS REVISED METHOD OF
 ASSESSING WIND LOAD, THE BASIC VELOCITY
 PRESSURES WILL CHANGE.AMEND THE NOTES
 TO REFLECT THIS.
  
 3) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED IN RESPECT OF THE MASONRY
 COLUMNS ON EACH SIDE OF THE PATIO DOOR
 FROM THE LIVING ROOM.SHEET A-02,
 FOUNDATION PLAN AND SHEET A-03, FLOOR
 PLAN ARE STILL SHOWING DIFFERENT COLUMN
 TYPES.AMEND SHEET A-03 TO RECTIFY.
  
 12) THIS COMMENT HAS NOT BEEN ADDRESSED.
 ADD A NOTE TO THE PLANS TO STATE THE
 REQUIREMENT FOR HURRICANE IMPACT
 SHUTTERS.
  
 13) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SUBMIT A PRODUCT APPROVAL FOR THE
 GARAGE DOOR.
  
 14) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE DRAWING SHEETS 1 THROUGH 15 WHICH
 SHOULD ACCOMPANY THE GARAGE DOOR PRODUCT
 APPROVAL ARE STILL MISSING.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499