Notes |
Date |
Text |
2002-03-27 00:00:00 | DENIED | | REFERENCE: FBC-2001 | | | | 1) SHT A-02 FROM PREVIOUS REVIEW, BATH | | #2 EVERY DRY VENT CONNECTING TO A HORI- | | ZONTAL DRAIN SHALL CONNECT ABOVE THE | | CENTERLINE OF THE HORIZONTAL PIPE. SEC | | 904.5.3 | | 2) SHT A-02 FROM PREVIOUS REVIEW, WASH | | MACHINE - "S" TRAP NOT APPROVED. DRY | | VENT SEC 904.5.3 | | 3) SHT A-02 DRY VENT AT M/BATH SHOWER. | | SEC 904.5.3 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|