Plan Review Notes
Plan Review Notes For Permit 02011614
Permit Number 02011614
Review Stop M
Sequence Number 2
Notes
Date Text
2002-03-21 00:00:00 
 MECHANICAL PLANS WERE NOT RESUBMITTED
 FOR REVIEW.
  
 FRESH AIR INTAKE INDICATED ON PLAN
 SHEETA-03.PLEASE NOTE INTAKE OPENINGS
 THAT TERMINATE OUTDOORS SHALL BE
 PROTECTED WITH CORROSION RESISTANT
 SCREENS, LOUVERS OR GRILLES. OPENINGS IN
 LOUVERS, GRILLES AND SCREENS SHALL BE
 SIZED IN ACCORDANCE WITH TABLE 401.6.
 (2001 SBC, MECH 401.6)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.