2002-03-04 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) THIS IS A PLAN REVIEW FOR A MASTER |
| MODEL.REMOVE THE SITE SPECIFIC SURVEY |
| DRAWING BEFORE RESUBMITTAL. |
| |
| 2) ALL PERMIT APPLICATIONS REVIEWED WITH |
| REFERENCE TO THIS MASTER WILL BE CHECKED |
| FOR COMPLIANCE WITH THE CURRENT CODE, |
| FLORIDA BUILDING CODE.THE MASTER HAS |
| BEEN REVIEWED FOR COMPLIANCE WITH THAT |
| CODE, SO ALL REFERENCES TO THE 'STANDARD |
| BUILDING CODE' MUST BE REMOVED.ALSO, |
| THE GENERAL NOTES (SHEET G1) AND ROOF |
| FRAMING NOTES (SHEET A-05) MUST BE |
| AMENDED TO REFLECT WIND LOAD ASSESSMENT |
| IN ACCORDANCE WITH THE FLORIDA BUILDING |
| CODE 2001. |
| |
| 3) SHEET A-02, FOUNDATION PLAN.THE |
| MASONRY COLUMNS ON EACH SIDE OF THE |
| OVERHEAD GARAGE DOOR AND THE SLIDING |
| GLASS PATIO DOOR FROM THE LIVING ROOM |
| ARE TYPE C2. THE FLOOR PLAN (SHEET A-03) |
| SHOWS C1 COLUMNS IN THESE LOCATIONS. |
| AMEND THE PLAN TO CLEAR THIS DISCREPANCY |
| |
| 4) THE KITCHEN WINDOW IS SHOWN AS TYPE H |
| ON THE PLANS AND TYPE M ON THE ELEVATION |
| PROVIDE THE CORRECT REFERENCE. |
| |
| 5) PLEASE NOTE THAT, FOR THE PERMIT |
| APPLICATIONS BASED ON THIS MODEL, THE |
| WINDOWS FACING LOT LINES MAY NEED TO BE |
| FIRE-RATED IN ACCORDANCE WITH TABLE 600, |
| IF CLOSE TO THE COMMON PROPERTY LINE. |
| |
| 6) SHEET A-05, ROOF FRAMING PLAN. THE |
| BEAM OVER THE FRONT ENTRANCE DOOR IS |
| REFERENCED AS TYPE 8F81B.THIS |
| REFERENCE IS NOT INCLUDED ON THE 'BEAM |
| SCHEDULE'. |
| |
| 7) SHEET A-05, ROOF FRAMING PLAN.FOUR |
| OF THE TRUSS ANCHOR LABELS/NOTES AT THE |
| LEFT ELEVATION HAVE BEEN PARTIALLY |
| PRINTED AND ARE NOT LEGIBLE. |
| |
| 8) TRUSS ANCHOR SCHEDULE. |
| USP RT161T IS NOT A VALID USP REFERENCE. |
| SIMPSON MTT27B IS NOT VALID REFERENCE. |
| ALSO, FOR THE USP NFM, STATE THE MINIMUM |
| REQUIRED SPECIFICATION/REFERENCE. |
| |
| 9) FBC 2309.7CROSS VENTILATION SHALL |
| BE PROVIDED FOR EACH SEPARATE ATTIC |
| SPACE.AT LEAST 50% OF THE REQUIRED |
| VENTILATION AREA SHALL BE AT A LEVEL NO |
| LESS THAN 3FT ABOVE THE EAVES VENTS. |
| |
| 10) THE SUBMITTED ROOF TILE PRODUCT |
| APPROVAL FOR INTERLOCKING ROLL CONCRETE |
| TILES DOES NOT CORRELATE TO THE |
| ELEVATIONS WHICH SHOW "SPANISH S CEMENT |
| TILE".SUBMIT AN APPROPRIATE PRODUCT |
| APPROVAL. |
| |
| 11) FBC 1606.3.3SPECIFY ROOF TILE |
| FASTENINGS. |
| |
| 12) FBC 1606.1.4THE SUBMITTED PRODUCT |
| APPROVAL FOR GLASS BLOCK WINDOWS |
| REQUIRES THE INSTALLTION OF HURRICANE |
| MISSILE IMPACT PROTECTION.ADD A NOTE |
| TO THE PLANS STATING THE REQUIREMENT FOR |
| HURRICANE IMPACT SHUTTERS. |
| |
| 13) FBC 1606.1.4SUBMIT A PRODUCT |
| APPROVAL FOR THE GARAGE DOOR. |
| |
| 14) PRODUCT APPROVAL (ACCEPTANCE |
| NUMBER 00-0307.04) FOR THE '20 GAUGE |
| GALVANISED STEEL STORM SHUTTER'. DRAWING |
| SHEETS 1 THROUGH 15 (INCL SHEET 10A) ARE |
| MISSING. |
| |
| 15) THE DOOR SCHEDULE STATES THAT THE |
| FRONT ENTRANCE DOOR IS WOOD.THE |
| SUBMITTED PRODUCT APPROVAL IS FOR STEEL |
| DOORS.IF THIS IS THE CORRECT PRODUCT |
| APPROVAL, AMEND THE DOOR SCHEDULE TO |
| REFLECT THIS. |
| |
| 16) FBC 13-103.1.2THE ARCHITECT, OWNER |
| OR HIS/HER LEGALLY DESIGNATED AGENT |
| SHALL SIGN THE SUBMITTED ENERGY CODE |
| COMPLIANCE CERTIFICATE. |
| |
| 17) FBC 13-603.1.ABC.1THE GARAGE DOOR |
| FALLS WITHIN THE DEFINITION OF AN |
| 'ADJACENT' DOOR (SECT. 202DEFINITIONS) |
| AND SHALL BE SOLID CORE OR INSULATED. |
| THE DOOR SCHEDULE REFERENCE MARK GIVEN |
| IS '8' WHICH IS SHOWN AS A TYPE F DOOR. |
| THE DOOR TYPE ELEVATIONS SHOW TYPE F AS |
| BEING A DOUBLE DOOR. CORRECTION REQUIRED |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |