2002-03-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THIS IS A PLAN REVIEW FOR A MASTER
 MODEL.REMOVE THE SITE SPECIFIC SURVEY
 DRAWING BEFORE RESUBMITTAL.
  
 2) ALL PERMIT APPLICATIONS REVIEWED WITH
 REFERENCE TO THIS MASTER WILL BE CHECKED
 FOR COMPLIANCE WITH THE CURRENT CODE,
 FLORIDA BUILDING CODE.THE MASTER HAS
 BEEN REVIEWED FOR COMPLIANCE WITH THAT
 CODE, SO ALL REFERENCES TO THE 'STANDARD
 BUILDING CODE' MUST BE REMOVED.ALSO,
 THE GENERAL NOTES (SHEET G1) AND ROOF
 FRAMING NOTES (SHEET A-05) MUST BE
 AMENDED TO REFLECT WIND LOAD ASSESSMENT
 IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE 2001.
  
 3) SHEET A-02, FOUNDATION PLAN.THE
 MASONRY COLUMNS ON EACH SIDE OF THE
 OVERHEAD GARAGE DOOR AND THE SLIDING
 GLASS PATIO DOOR FROM THE LIVING ROOM
 ARE TYPE C2. THE FLOOR PLAN (SHEET A-03)
 SHOWS C1 COLUMNS IN THESE LOCATIONS.
 AMEND THE PLAN TO CLEAR THIS DISCREPANCY
  
 4) THE KITCHEN WINDOW IS SHOWN AS TYPE H
 ON THE PLANS AND TYPE M ON THE ELEVATION
 PROVIDE THE CORRECT REFERENCE.
  
 5) PLEASE NOTE THAT, FOR THE PERMIT
 APPLICATIONS BASED ON THIS MODEL, THE
 WINDOWS FACING LOT LINES MAY NEED TO BE
 FIRE-RATED IN ACCORDANCE WITH TABLE 600,
 IF CLOSE TO THE COMMON PROPERTY LINE.
  
 6) SHEET A-05, ROOF FRAMING PLAN. THE
 BEAM OVER THE FRONT ENTRANCE DOOR IS
 REFERENCED AS TYPE 8F81B.THIS
 REFERENCE IS NOT INCLUDED ON THE 'BEAM
 SCHEDULE'.
  
 7) SHEET A-05, ROOF FRAMING PLAN.FOUR
 OF THE TRUSS ANCHOR LABELS/NOTES AT THE
 LEFT ELEVATION HAVE BEEN PARTIALLY
 PRINTED AND ARE NOT LEGIBLE.
  
 8) TRUSS ANCHOR SCHEDULE.
 USP RT161T IS NOT A VALID USP REFERENCE.
 SIMPSON MTT27B IS NOT VALID REFERENCE.
 ALSO, FOR THE USP NFM, STATE THE MINIMUM
 REQUIRED SPECIFICATION/REFERENCE.
  
 9) FBC 2309.7CROSS VENTILATION SHALL
 BE PROVIDED FOR EACH SEPARATE ATTIC
 SPACE.AT LEAST 50% OF THE REQUIRED
 VENTILATION AREA SHALL BE AT A LEVEL NO
 LESS THAN 3FT ABOVE THE EAVES VENTS.
  
 10) THE SUBMITTED ROOF TILE PRODUCT
 APPROVAL FOR INTERLOCKING ROLL CONCRETE
 TILES DOES NOT CORRELATE TO THE
 ELEVATIONS WHICH SHOW "SPANISH S CEMENT
 TILE".SUBMIT AN APPROPRIATE PRODUCT
 APPROVAL.
  
 11) FBC 1606.3.3SPECIFY ROOF TILE
 FASTENINGS.
  
 12) FBC 1606.1.4THE SUBMITTED PRODUCT
 APPROVAL FOR GLASS BLOCK WINDOWS
 REQUIRES THE INSTALLTION OF HURRICANE
 MISSILE IMPACT PROTECTION.ADD A NOTE
 TO THE PLANS STATING THE REQUIREMENT FOR
 HURRICANE IMPACT SHUTTERS.
  
 13) FBC 1606.1.4SUBMIT A PRODUCT
 APPROVAL FOR THE GARAGE DOOR.
  
 14) PRODUCT APPROVAL (ACCEPTANCE
 NUMBER 00-0307.04) FOR THE '20 GAUGE
 GALVANISED STEEL STORM SHUTTER'. DRAWING
 SHEETS 1 THROUGH 15 (INCL SHEET 10A) ARE
 MISSING.
  
 15) THE DOOR SCHEDULE STATES THAT THE
 FRONT ENTRANCE DOOR IS WOOD.THE
 SUBMITTED PRODUCT APPROVAL IS FOR STEEL
 DOORS.IF THIS IS THE CORRECT PRODUCT
 APPROVAL, AMEND THE DOOR SCHEDULE TO
 REFLECT THIS.
  
 16) FBC 13-103.1.2THE ARCHITECT, OWNER
 OR HIS/HER LEGALLY DESIGNATED AGENT
 SHALL SIGN THE SUBMITTED ENERGY CODE
 COMPLIANCE CERTIFICATE.
  
 17) FBC 13-603.1.ABC.1THE GARAGE DOOR
 FALLS WITHIN THE DEFINITION OF AN
 'ADJACENT' DOOR (SECT. 202DEFINITIONS)
 AND SHALL BE SOLID CORE OR INSULATED.
 THE DOOR SCHEDULE REFERENCE MARK GIVEN
 IS '8' WHICH IS SHOWN AS A TYPE F DOOR.
 THE DOOR TYPE ELEVATIONS SHOW TYPE F AS
 BEING A DOUBLE DOOR. CORRECTION REQUIRED
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS