Plan Review Notes
Plan Review Notes For Permit 02011614
Permit Number 02011614
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-05 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) PLEASE INDICATE CODE PLAN ARE DESIGN-
 ED FOR ON PLANS.
 2) SHT A-02 BATH #2, EVERY DRY VENT CON-
 NECTING TO A HORIZONTAL DRAIN SHALL CON-
 ECT ABOVE THE CENTERLINE OF THE HORIZON-
 TAL PIPE. SEC 904.5.3
 3) SHT A-02 BATH #2,3" PIPE NOT ALLOW-
 ED IN BLOCK WALL - TIE BEAM. FBC-2001
 SEC 1907.3.5.
 4) SHT A-02 BATH #2, LAV NOT VENTED.
 5) SHT A-02 WASHING MACHINE, TRAP UNDER-
 GROUND? DRY HORIZONTAL VENT SEC 904.5.3
 6) SHT A-02 MASTER BATH SHOWER NOT VENT-
 ED.
 7) SHT A-02 MASTER BATH, 3" PIPE NOT
 ALLOWED IN BLOCK WALL - TIE BEAM. FBC
 SED 1907.3.5
 8) SHT A-02 KITCHEN DRY HORIZONTAL VENT
 SEC 904.5.3
 9) SHT A-02 KITCHEN, "S" TRAPS NOT APPRO
 VEN.
 10) SHT A-02 KITCHEN, DISHWASHER NOT
 TRAPPED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377