Plan Review Notes For Permit 02011614 |
Permit Number |
02011614 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-03-05 00:00:00 | DENIED | | REFERENCE: FBC-2001 | | | | 1) PLEASE INDICATE CODE PLAN ARE DESIGN- | | ED FOR ON PLANS. | | 2) SHT A-02 BATH #2, EVERY DRY VENT CON- | | NECTING TO A HORIZONTAL DRAIN SHALL CON- | | ECT ABOVE THE CENTERLINE OF THE HORIZON- | | TAL PIPE. SEC 904.5.3 | | 3) SHT A-02 BATH #2,3" PIPE NOT ALLOW- | | ED IN BLOCK WALL - TIE BEAM. FBC-2001 | | SEC 1907.3.5. | | 4) SHT A-02 BATH #2, LAV NOT VENTED. | | 5) SHT A-02 WASHING MACHINE, TRAP UNDER- | | GROUND? DRY HORIZONTAL VENT SEC 904.5.3 | | 6) SHT A-02 MASTER BATH SHOWER NOT VENT- | | ED. | | 7) SHT A-02 MASTER BATH, 3" PIPE NOT | | ALLOWED IN BLOCK WALL - TIE BEAM. FBC | | SED 1907.3.5 | | 8) SHT A-02 KITCHEN DRY HORIZONTAL VENT | | SEC 904.5.3 | | 9) SHT A-02 KITCHEN, "S" TRAPS NOT APPRO | | VEN. | | 10) SHT A-02 KITCHEN, DISHWASHER NOT | | TRAPPED. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|