2002-03-05 00:00:00 | MODEL A "MASTER" - PLANS REVIEWED UNDER | | THE 2001 FLORIDA BUILDING CODE, | | MECHANICAL. | | | | | | | | 1.SHOW COMPLIANCE WITH TABLE 403.3 OF | | THE 2001 FBC, MECHANICAL, REQUIRED | | OUTSIDE AIR FOR PRIVATE DWELLING | | SINGLE & MULTIPLE LIVING AREAS. | | | | 2.INDICATE LOCATION, SIZE AND MATERIAL | | OF OUTSIDE AIR DUCT. | | | | 3.AIR TRANSFER REQUIRED FOR BEDROOM | | 2 FOR COMPLIANCE WITH 2001 FBC, MECH | | 601.4 (BALANCED AIR RETURN). | | | | 4.PLAN SHEET E-1 INDICATES A 5 TON | | A/C AND HVAC PLAN INDICATES A 3 1/2 | | TON A/C.PLEASE CORRELATE PLANS. | | | | 5.OVERFLOW PROTECTION REQUIRED.SHOW | | COMPLIANCE WITH 2001 FBC, MECH | | 307.2.3 OR 307.2.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|