2002-03-06 00:00:00 | ***************** UNSAT *************** |
| |
| 1)NOTE: PLEASE NOTE THAT RISER SHOWS AN |
| EQUIPMENT GROUNDING CONDUCTOR FROM |
| METER TO MAIN DISC? PLEASE NOTE THAT |
| THIS PARALLELING THE NEUTRAL. |
| |
| 2) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| |
| 3) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| |
| 4)NOTE: PLEASE NOTE MISSING GFI OUTLET |
| FOR PENINSULAR IN KITCHEN. 210-52-C-3 |
| |
| 5)NOTE: PLEASE NOTE MISSING EGRESS LIGHT |
| -ING IN MANY LOCATIONS. PER 210-70 |
| PLEASE CLARIFYIF THERE IS AN ATTIC |
| ACCESS IN MASTER BEDROOM CLOSET? IF YES, |
| THEN A LT IS REQ`D PER 210-70. |
| |
| 6)NOTE: PLEASE NOTE THAT A DEDICATED |
| CIRCUIT IS SHOWN ON PANEL SCHEDULE FOR |
| WHIRLPOOL AND LOCATION OF REC IS NOT |
| SHOWN ON PLANS? PLEASE SHOW. |
| |
| 7)NOTE: PLEASE NOTE THAT DERATING OF |
| A/C AHU HEAT IS TAKEN TWICE AT 65%, |
| PLEASE NOT ONLY ONE DEDUCTION IS |
| PERMITTED. |
| |
| 8)NOTE: PLEASE NOTE THAT PLANS SHOW |
| VOLTAGE BEING 120V? PLEASE NOTE THAT |
| SERVICE SHOULD BE 120/240V. |
| PLEASE NOTE THAT LOAD SHOWN EXCEEDS |
| 200A RATING OF PANEL. |
| |
| 9)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| PROTECTION PER 210-12. LIST ON PANEL |
| SCHEDULE. |
| |
| 10)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| GOING TO BUILDING STEEL AND COLD WATER |
| PER 250-50. |
| MISSING BLDG/FOOTER STEEL. |
| |
| 11)NOTE: PLEASE VERFIY CODE ARTS SHOWN |
| IN NOTES. PLEASE NOTE THAT BATH ART IS |
| SHOWN FOR KITCHEN NOTE AND ART FOR BATH |
| NOTE SHOULD BE 210-11-C-3. |
| PLEASE CORRELATE.. |
| |
| PLEASE SUBMIT THE ABOVE INFORMAITON FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |