2002-03-06 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) GENERAL NOTES #1 THE CURRENT CODE IS
 FBC-2001, SEC 424.2.6 ENGINEERING DESIGN
 NOT SBCCI-94 PBC SWIMMING POOL CODE.
 2) NOTE #5 DISPOSAL OF WATER. SEE FBC
 2001, SEC 424.2.10 WASTE WATER DISPOSAL.
 3) NOTE #7 WATER SUPPLY. SEE FBC 2001
 SEC 424.2.9 WATER SUPPLY, AND LOCAL ORD
 #2853-95 BACKFLOW PREVENTER REQUIRED ON
 WATER SERVICE.
 4) POOL, SPA SCHEMATIC NOT APPROVED.
 SPA MAIN DRAIN NOT SHOWN ON SCHEMATIC.
 INDICATE VENTS FOR MAIN DRAINS AND VAC
 LINE ON SCHEMATIC.
 5) FLA ENERGY CODE SEC 612.1ABC 2.3.2
 SPAS, HEATED POOLS SHALL BE EQUIPED WITH
 A COVER TO MINIMIZE HEAT LOSS.
 6) FBC-2001 SEC 424.2.13.2 JOINTS, CON-
 NECTIONS. PURPLE PRIMER REQUIRED ON PVC
 PIPING, FBC 2001 PLUMBING, SEC 605.21
 7) ANY CHANGES ON SIGNED AND SEALED
 PLANS SHALL BE REDRAWN, RESIGNED AND RE-
 SEALED, OR CHANGES SHALL BE INITIALED
 AND DATED BY ENGINEER OF RECORD.
 8) FBC 2001 SEC 424.2.6.6.2 SHOW DETAIL
 FOR TESTING AND ACCEPTING BY RECOGNIZED
 TESTING FACILITY FOR ALL SUCTION FITT-
 INGS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377