Plan Review Notes For Permit 02011590 |
Permit Number |
02011590 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-03-06 00:00:00 | DENIED | | REFERENCE: FBC-2001 | | | | 1) GENERAL NOTES #1 THE CURRENT CODE IS | | FBC-2001, SEC 424.2.6 ENGINEERING DESIGN | | NOT SBCCI-94 PBC SWIMMING POOL CODE. | | 2) NOTE #5 DISPOSAL OF WATER. SEE FBC | | 2001, SEC 424.2.10 WASTE WATER DISPOSAL. | | 3) NOTE #7 WATER SUPPLY. SEE FBC 2001 | | SEC 424.2.9 WATER SUPPLY, AND LOCAL ORD | | #2853-95 BACKFLOW PREVENTER REQUIRED ON | | WATER SERVICE. | | 4) POOL, SPA SCHEMATIC NOT APPROVED. | | SPA MAIN DRAIN NOT SHOWN ON SCHEMATIC. | | INDICATE VENTS FOR MAIN DRAINS AND VAC | | LINE ON SCHEMATIC. | | 5) FLA ENERGY CODE SEC 612.1ABC 2.3.2 | | SPAS, HEATED POOLS SHALL BE EQUIPED WITH | | A COVER TO MINIMIZE HEAT LOSS. | | 6) FBC-2001 SEC 424.2.13.2 JOINTS, CON- | | NECTIONS. PURPLE PRIMER REQUIRED ON PVC | | PIPING, FBC 2001 PLUMBING, SEC 605.21 | | 7) ANY CHANGES ON SIGNED AND SEALED | | PLANS SHALL BE REDRAWN, RESIGNED AND RE- | | SEALED, OR CHANGES SHALL BE INITIALED | | AND DATED BY ENGINEER OF RECORD. | | 8) FBC 2001 SEC 424.2.6.6.2 SHOW DETAIL | | FOR TESTING AND ACCEPTING BY RECOGNIZED | | TESTING FACILITY FOR ALL SUCTION FITT- | | INGS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|