2002-02-28 00:00:00DENIED
 REFERENCE: FLA. BLD. CODE - 2001 - POOLS
  
 1) 424.2.6.2 EQUIPMENT LIST WITH MFG.
 CUT SHEETS.
 2) 424.2.6.4 MORE MFG. INFO REQUIRED,
 GIVE MFG RECOMMENDATIONS PLUS LISTING
 AGENCY APPROVAL.
 3) 424.2.6.6.2 SHOW ANSI/ASME A112.19.8M
 SUCTION FITTINGS COVERS INFO FOR ACCEPT-
 ANCE.
 4) 424.2.6.6.3 VENT NOT SHOWN FOR SPA
 MAIN DRAIN OR VACUUM LINE. ARE #'S 1 OR
 2 BEING USED? PLEASE PROVIDE DETAILS.
 5) 424.6.6.5 6" TO 12" BELOW MIN WATER L
 LEVEL. SHOW DETAILS OR STATE ON PLANS.
 6) 424.2.14.2 WATER RETENTION, NOT ABLE
 TO RETAIN WATER IN HEATER WITH ONLY ONE
 VALVE LOCATED WHERE SHOWN.
  