Plan Review Notes For Permit 02011590 |
Permit Number |
02011590 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-02-28 00:00:00 | DENIED | | REFERENCE: FLA. BLD. CODE - 2001 - POOLS | | | | 1) 424.2.6.2 EQUIPMENT LIST WITH MFG. | | CUT SHEETS. | | 2) 424.2.6.4 MORE MFG. INFO REQUIRED, | | GIVE MFG RECOMMENDATIONS PLUS LISTING | | AGENCY APPROVAL. | | 3) 424.2.6.6.2 SHOW ANSI/ASME A112.19.8M | | SUCTION FITTINGS COVERS INFO FOR ACCEPT- | | ANCE. | | 4) 424.2.6.6.3 VENT NOT SHOWN FOR SPA | | MAIN DRAIN OR VACUUM LINE. ARE #'S 1 OR | | 2 BEING USED? PLEASE PROVIDE DETAILS. | | 5) 424.6.6.5 6" TO 12" BELOW MIN WATER L | | LEVEL. SHOW DETAILS OR STATE ON PLANS. | | 6) 424.2.14.2 WATER RETENTION, NOT ABLE | | TO RETAIN WATER IN HEATER WITH ONLY ONE | | VALVE LOCATED WHERE SHOWN. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|