2002-03-14 00:00:00TRUSSES DENIED
  
 1)THE TRUSS DESIGN WIND LOAD INFORMATION
 IS NOT CONSISTENT. THE TRUSS DRAWING
 COVER SHEET LISTS 1997 SBC 110MPH AND
 MOST OF THE DRAWINGS LIST ASCE 7-98 AND
 140MPH WIND LOAD AND 15' MEAN ROOF
 HEIGHT. DRAWING #21 LISTS 1997 SBC AND
 110 MPH. THE STRUCTURE IS DESIGNED USING
 THE 1997 SBC WITH 110MPH AND 16' M.R.H.
 PLEASE CORRECT.
  
 2) THE UPLIFTS GIVEN ON THE TRUSS
 DRAWINGS EXCEED THE CAPACITIES OF
 SEVERAL OF THE SPECIFIED TRUSS ANCHORS.
 TRUSSES FB1, SG3 AND HGA.
 THE ANCHOR SPECIFIED FOR JOINT 13 OF
 TRUSS T26 WILL NOT WORK. THE TRUSS SITS
 ON TOP OF THE WALL AND A TRUSS HANGER IS
 SPECIFIED. PLEASE CORRECT.
  
 HUGHES AND SEMCO WERE PURCHASED BY USP.
 PLEASE UPDATE THE ANCHOR LEGEND AND
 HUGHES JOIST HANGER SPECIFIED ON SHEET 7
 TO REFLECT THIS CHANGE.