Plan Review Notes
Plan Review Notes For Permit 02011492
Permit Number 02011492
Review Stop E
Sequence Number 1
Notes
Date Text
2002-01-30 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 ALSO MISSING AN EQUIPMENT GROUNDING
 CONDUCTOR BETWEEN MAIN AND PANEL.
 CAN CE DRAWN IN/REDLINED. 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372