2002-02-07 00:00:00****************PROVISO!****************
  
 PLEASE NOTE THERE ARE NO BATH CIRCUITS
 LISTED ON THE PANEL SCHEDULE.COMPLY
 WITH 210-11(C)(3).NOTE SAME ON PANEL
 SCHEDULE.
  
 COMPLY WITH 347-4 IF USING PVC.(RISER
 DIAGRAM).
  
 PLEASE REMEDY THESE ISSUES BEFORE
 CALLING ROUGH INSPECTION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 (561) 659-0896 EXT.8392