Date Text
2002-02-11 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A-2 DOOR SHALL NOT SWING INTO
 CLEAR FLOOR SPACE OR TURNING RADIUS PER
 FACBC SECS 4.22.2 & 4.22.3
 2) SHT P-1 SANITARY RISER DIAGRAM. DRINK
 ING FOUNTAIN NOT SHOWN ON RISER DIAGRAM.
 3) SHT P-1 PLEASE PROVIDE A WATER RISER
 DIAGRAM. SHOW PIPE SIZE AND LOCATION
 OF WATER HAMMER ARRESTORS. ARRESTORS
 SHALL BE LOCATED NEAR FIXTURES IN AN
 "EFFECTIVE RANGE" AND NOT AT TOP OF DROP
 4) SHT P-1 PLEASE INDICATE HOW CONDEN-
 SATE WILL TERMINATE OUTSIDE OF BLDG. IF
 TIED INTO A DRYWELL OR STORM A RELIEF
 VENT SHALL BE INSTALLED IN DRAIN LINE
 WHERE IT EXITS BLDG. PLEASE SHOW DETAIL
 WITH CONDENSATE RISER DIAGRAM.
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377.