Plan Review Notes For Permit 02011349 |
Permit Number |
02011349 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-11 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) SHT A-2 DOOR SHALL NOT SWING INTO | | CLEAR FLOOR SPACE OR TURNING RADIUS PER | | FACBC SECS 4.22.2 & 4.22.3 | | 2) SHT P-1 SANITARY RISER DIAGRAM. DRINK | | ING FOUNTAIN NOT SHOWN ON RISER DIAGRAM. | | 3) SHT P-1 PLEASE PROVIDE A WATER RISER | | DIAGRAM. SHOW PIPE SIZE AND LOCATION | | OF WATER HAMMER ARRESTORS. ARRESTORS | | SHALL BE LOCATED NEAR FIXTURES IN AN | | "EFFECTIVE RANGE" AND NOT AT TOP OF DROP | | 4) SHT P-1 PLEASE INDICATE HOW CONDEN- | | SATE WILL TERMINATE OUTSIDE OF BLDG. IF | | TIED INTO A DRYWELL OR STORM A RELIEF | | VENT SHALL BE INSTALLED IN DRAIN LINE | | WHERE IT EXITS BLDG. PLEASE SHOW DETAIL | | WITH CONDENSATE RISER DIAGRAM. | | | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377. |
|