Plan Review Notes For Permit 02011286 |
Permit Number |
02011286 |
|
Review Stop |
E |
Sequence Number |
7 |
|
Notes |
Date |
Text |
2002-12-03 00:00:00 | *************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE, NOW AHU HAS BEEN | | ADDED TO PANEL "A" BUT IS STILL SHOWN | | ON PANEL "C"? PLEASE CLARIFY.PLEASE ALSO | | NOTE, OCP IS SHOWN AT 2-P 60 FOR 5KW | | HEAT. PLEASE VERFIY MAX OCP FOR 5KW. | | | | 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE | | LOAD SHOWN AND LOAD SHOWN ON LOAD CALCS | | FOR PANEL "C".PANEL "C" SHOWS 31.04KVA? | | | | 3)NOTE: PLEASE NOTE, IF LOADS ARE | | FIGURED AT ALL CONNECTED LOADS THEN | | IT WILL TAKE IT OVER 400A'S. | | PLEASE SEE ART 220 FOR METHODS AND | | DERATING FACTORS PERMITTED. | | | | 4)NOTE: PLEASE SEE 1/2" CONDUITS SHOWN | | FROM METER TO PANEL "A' AND METER TO FPL | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|