Plan Review Notes For Permit 02011286
Permit Number 02011286
Review Stop E
Sequence Number 7
Notes
Date Text
2002-12-03 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE, NOW AHU HAS BEEN
 ADDED TO PANEL "A" BUT IS STILL SHOWN
 ON PANEL "C"? PLEASE CLARIFY.PLEASE ALSO
 NOTE, OCP IS SHOWN AT 2-P 60 FOR 5KW
 HEAT. PLEASE VERFIY MAX OCP FOR 5KW.
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 LOAD SHOWN AND LOAD SHOWN ON LOAD CALCS
 FOR PANEL "C".PANEL "C" SHOWS 31.04KVA?
  
 3)NOTE: PLEASE NOTE, IF LOADS ARE
 FIGURED AT ALL CONNECTED LOADS THEN
 IT WILL TAKE IT OVER 400A'S.
 PLEASE SEE ART 220 FOR METHODS AND
 DERATING FACTORS PERMITTED.
  
 4)NOTE: PLEASE SEE 1/2" CONDUITS SHOWN
 FROM METER TO PANEL "A' AND METER TO FPL
  
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372