Plan Review Notes For Permit 02011286 |
Permit Number |
02011286 |
|
Review Stop |
E |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2002-11-21 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE, PER 700-12E, | | EM/EX LTS NEED TO BE ON THE SAME | | CIRCUITS AS NORMAL LIGHTING IN THOSE | | AREAS. | | PLEASE CORRELATE CIRCUITS AND PANEL | | SCHEDULE. | | | | 2)NOTE: PLEASE NOTE, ONLY ONE AHU IS | | SHOWN ON PANEL "A". | | TWO AIR COMP #1`S SHOWN. | | | | 3)NOTE: PLEASE NOTE KW LOAD SHOWN FOR | | COND UNITS. PLEASE VERIFY LOADS AND | | CORRELATE OCP PER 424-3. | | | | 4)NOTE: PLEASE LABEL PANELS ACCORDING TO | | PANEL SCHEDULES. "A,B,C". | | | | 5)NOTE: PLEASE VERIFY 2-SD`S SHOWN | | OUTSIDE MECH CLOSET? FIRE REVIEW COMMENT | | . | | | | 6)NOTE: PLEASE RE-CONFIGURE LOAD | | CALCULATIONS PER NEC220-3,220-10, | | 220-11,220-13 ETC. PLEASE NOTE, LOADS | | SHOWN FOR PANEL "C" SHOWN AT 4.29AMPS. | | IF LOADS ARE ADDED AS SHOWN, SERVICE | | LOAD COMES UP TO 450.875 WHICH EXCEEDS | | SERVICE SIZE/WIRE ETC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|