2002-11-21 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE, PER 700-12E,
 EM/EX LTS NEED TO BE ON THE SAME
 CIRCUITS AS NORMAL LIGHTING IN THOSE
 AREAS.
 PLEASE CORRELATE CIRCUITS AND PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE NOTE, ONLY ONE AHU IS
 SHOWN ON PANEL "A".
 TWO AIR COMP #1`S SHOWN.
  
 3)NOTE: PLEASE NOTE KW LOAD SHOWN FOR
 COND UNITS. PLEASE VERIFY LOADS AND
 CORRELATE OCP PER 424-3.
  
 4)NOTE: PLEASE LABEL PANELS ACCORDING TO
 PANEL SCHEDULES. "A,B,C".
  
 5)NOTE: PLEASE VERIFY 2-SD`S SHOWN
 OUTSIDE MECH CLOSET? FIRE REVIEW COMMENT
 .
  
 6)NOTE: PLEASE RE-CONFIGURE LOAD
 CALCULATIONS PER NEC220-3,220-10,
 220-11,220-13 ETC. PLEASE NOTE, LOADS
 SHOWN FOR PANEL "C" SHOWN AT 4.29AMPS.
 IF LOADS ARE ADDED AS SHOWN, SERVICE
 LOAD COMES UP TO 450.875 WHICH EXCEEDS
 SERVICE SIZE/WIRE ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW