2002-07-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE NECESSARY CHANGES ON THE
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE SERVICE ENTRANCE CONDUCTORS IN TH
 E 2 1/2"CONDUIT EXCEED PERMISSIBLE CONDU
 IT FILL PER APPENDIX "C",CHAPTER 9.THIS
 IS THE SAME COMMENT THAT WAS ON THE NOTE
 S FROM THE PREVIOUS REVIEW,IF THERE IS A
 QUESTION ON THIS ,PLEASE CALL.
  
 2} THE RISER DIAGRAM SHOWS 3/0,S FROM 30
 0 AMP MAIN,PLEASE CLARIFY.SAME NOTE AS P
 REVIOUS REVIEW.
  
 3} MISSING EQUIPMENT GROUND CONDUCTOR BE
 TWEEN BOTH MAIN DISCONNECTS AND PANELS.