Plan Review Notes For Permit 02011286 |
Permit Number |
02011286 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-06-05 00:00:00 | ************ UNSAT ************** | | | | 1)NOTE: PLEASE NOTE SERVICE ENTRANCE | | CONDUCTORS HAVE NOW CHANGED, PLEASE NOTE | | CONDUIT FILL IN NEC TABLE, 6 350MCM IN | | A 2 1/2 CONDUIT. CHAPTER 9 | | | | 2)NOTE: PLEASE CLARIFY 350MCMS GOING | | THROUGHT 300A DISC AND FEEDING 100A | | DISC. PLEASE VERFIY 350MCM FOR 100AMPS?? | | YET RISER SHOWS 3/0`S FROM 300MAIN BRKR | | TO 100A MAIN?? PLEASE CLARIFY HOW | | WIRE SIZES APPEAR TO CHANGE FROM 350MCM | | TO 3/0`S? IN 300A DISC. | | PLEASE ALSO NOTE 3/0`S OR 350MCM BEING | | ABLE TO FIT UNDER 100A MCB?240-6/310- | | -16.215-5 ETC. | | 3)NOTE: PLEASE NOTE STILL MISSING | | EQUIPMENT GROUNDING BETWEEN BOTH MAIN | | DISC`S AND PANELS. 250-122 | | | | 4)NOTE: PLEASE SEE ATTACHMENT OF FS/FAC | | 553-79 (2)(B) IN REFERENCE TO PLANS | | BEING REVIEW FOR THE SAME COMMENTS AFTER | | 3RD REVIEW. SEE ATTACHED. | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|