Plan Review Notes For Permit 02011286 |
Permit Number |
02011286 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-04-05 00:00:00 | **************** UNSAT ***************** | | | | 1)NOTE: PLEASE NOTE THAT CONDUCTOR SIZE | | IS STILL NOT CORRECT. PLEASE NOTE THAT | | RISER DIAGRAM IS SHOWING 1/0`S FOR A | | 200AMP SERVICE. PLEASE SEE 310-16 FOR | | CORRECT SIZING. | | | | 2)NOTE: PLEASE NOTE THAT MISSING/CLARIFY | | EQUIPMENT GROUNDING METHOD/CONDCUTOR | | BETWEEN MAIN AND PANEL. SIZE PER 250-122 | | | | 3)NOTE: PLEASE NOTE THAT BRANCH CIRCUIT- | | -ING #`S ARE TO BE SHOWN ON PLANS AND | | CORRELATE WITH THE SUBMITTED PANEL | | SCHEDULE. | | | | 4)NOTE: PLEASE CLARIFY MANY LOADS ON | | PANEL SCHEDULE FOR 1-POLE 20A BRKRS | | SHOWN AT 2.4KW? PLEASE NOTE THAT,AT THAT | | LOAD, IT TAKE IT PAST THE NORMAL 80% | | LOADING OF A BRKR. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|