2002-04-05 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT CONDUCTOR SIZE
 IS STILL NOT CORRECT. PLEASE NOTE THAT
 RISER DIAGRAM IS SHOWING 1/0`S FOR A
 200AMP SERVICE. PLEASE SEE 310-16 FOR
 CORRECT SIZING.
  
 2)NOTE: PLEASE NOTE THAT MISSING/CLARIFY
 EQUIPMENT GROUNDING METHOD/CONDCUTOR
 BETWEEN MAIN AND PANEL. SIZE PER 250-122
  
 3)NOTE: PLEASE NOTE THAT BRANCH CIRCUIT-
 -ING #`S ARE TO BE SHOWN ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE.
  
 4)NOTE: PLEASE CLARIFY MANY LOADS ON
 PANEL SCHEDULE FOR 1-POLE 20A BRKRS
 SHOWN AT 2.4KW? PLEASE NOTE THAT,AT THAT
 LOAD, IT TAKE IT PAST THE NORMAL 80%
 LOADING OF A BRKR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372