Plan Review Notes
Plan Review Notes For Permit 02011286
Permit Number 02011286
Review Stop P
Sequence Number 1
Notes
Date Text
2002-02-11 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLEASE SPECIFY ON PLANS WHICH CODE
 PLANS WERE DESIGNED FOR.
 2) SHT A-1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT FLOOR PLAN.
 3) SHT A-1 SANITARY RISER DIAGRAM, FLOOR
 DRAIN IN WOMENS RESTROOM IN NOT VENTED
 PROPERLY.
 4) SHT A-1 SANT. RISER DIA. WATER COOLER
 SHOWN ON SANT RISER DIA. BY KITCHEN SINK
 NOT ON FLOOR PLAN?
 5) SHT A-2 PLEASE SHOW CLEAR FLOOR SPACE
 FOR HDCP FIXTURES.
 6) SHT A-2 DOOR CANNOT SWING INTO CLEAR
 FLOOR SPACE OR TURNING RADIUS. FACBC SEC
 4.22.2 & 4.22.3
 7) SHT A-2 DRINKING FOUNTAIN, IF SINGLE
 DRINKING FOUNTAIN, PROVISIONS SHALL BE
 PROVIDED FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING. FACBC SEC 4.1.3(10)
 8) SHT A-1 WATER RISER DIAGRAM DOES NOT
 REFLECT FLOOR PLAN. W/HEATER NOT BY REST
 ROOM BUT BY KITCHEN. PLEASE SUBMIT RISER
 THAT REFLECTS FLOOR PLAN.
 9) SHT A-2 BATHROOM EQUIP. #9 MINIMUM OF
 29" TO BOTTOM OF LAV NOT 28" AS SHOWN.
 10) PLEASE GIVE DETAIL FOR KITCHEN SINK
 SHOW COMPLIANCE FOR FACBC SEC 4.24.
  
 REVIEW BY KEN STEVENS