Plan Review Notes For Permit 02011286 |
Permit Number |
02011286 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-11 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) PLEASE SPECIFY ON PLANS WHICH CODE | | PLANS WERE DESIGNED FOR. | | 2) SHT A-1 SANITARY RISER DIAGRAM DOES | | NOT REFLECT FLOOR PLAN. | | 3) SHT A-1 SANITARY RISER DIAGRAM, FLOOR | | DRAIN IN WOMENS RESTROOM IN NOT VENTED | | PROPERLY. | | 4) SHT A-1 SANT. RISER DIA. WATER COOLER | | SHOWN ON SANT RISER DIA. BY KITCHEN SINK | | NOT ON FLOOR PLAN? | | 5) SHT A-2 PLEASE SHOW CLEAR FLOOR SPACE | | FOR HDCP FIXTURES. | | 6) SHT A-2 DOOR CANNOT SWING INTO CLEAR | | FLOOR SPACE OR TURNING RADIUS. FACBC SEC | | 4.22.2 & 4.22.3 | | 7) SHT A-2 DRINKING FOUNTAIN, IF SINGLE | | DRINKING FOUNTAIN, PROVISIONS SHALL BE | | PROVIDED FOR THOSE WHO HAVE DIFFICULTY | | BENDING OR STOOPING. FACBC SEC 4.1.3(10) | | 8) SHT A-1 WATER RISER DIAGRAM DOES NOT | | REFLECT FLOOR PLAN. W/HEATER NOT BY REST | | ROOM BUT BY KITCHEN. PLEASE SUBMIT RISER | | THAT REFLECTS FLOOR PLAN. | | 9) SHT A-2 BATHROOM EQUIP. #9 MINIMUM OF | | 29" TO BOTTOM OF LAV NOT 28" AS SHOWN. | | 10) PLEASE GIVE DETAIL FOR KITCHEN SINK | | SHOW COMPLIANCE FOR FACBC SEC 4.24. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|