Plan Review Notes
Plan Review Notes For Permit 02011286
Permit Number 02011286
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-02-01 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 3) MECHANICAL ROOM TO BE SEPARATED BY
 AT LEAST ONE HOUR FROM THE REMAINDER
 OF THE BUILDING.
 4) PLEASE INDICATE LOCATIONS OF FIRE
 HYDRANTS IN RELATION TO THE PROPOSED
 CLUBHOUSE.
 5) DUCT SMOKE DETECTORS ARE REQUIRED
 IN AIR HANDLING SYSTEMS OVER 2000 CFM.
 6) BUILDING SECTION 2 DISPLAYS STORAGE
 AREA BUT THE FLOOR PLAN DOES NOT, PLEASE
 CLARIFY.
 7) PLEASE INDICATE LOCATIONS OF PORTABLE
 FIRE EXTINGUISHERS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910