Plan Review Notes
Plan Review Notes For Permit 02011286
Permit Number 02011286
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-05 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THE CONDUCTOR SIZE
 SHOWN FOR BOTH 200AMP MAINS? PLEASE SEE
 310-16 FOR CORRECT WIRE SIZE.
 PLEASE NOTE THAT WITH CONDUCTOR SIZE
 CHANGING THEN CONDUIT SIZE IS REQ`D TO
 BE INCREASED.
  
 2)NOTE: PLEASE NOTE THAT PLANS ONLY
 SHOW ONE MAIN WITH METER ON THE OUTSIDE
 OF BLDG. PLEASE SHOW LOCATION OF SECOND
 DISCONNECT.
  
 3)NOTE: PLEASE NOTE 373-8 FOR USE OF THE
 MAIN AS RACEWAY.
  
 4)NOTE: PLEASE NOTE THAT PANEL "B" IS
 NOT SHOWN ON PLANS "PLEASE CLARIFY/ SHOW
 ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372