Plan Review Notes For Permit 02011248 |
Permit Number |
02011248 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-09-07 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) ONLY THE FIXTURES WITHIN THE BATHROOM | | GROUP SHALL CONNECT TO THE WET-VENTED | | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF | | THE WET VENT. 909.1 - THE LAUNDRY TRAY | | SHALL NOT DRAIN THROUGH THE BATHROOM | | GROUP. | | 2) SANITARY RISER SHALL REFLECT THE | | FLOOR PLAN. PLEASE SEE RED LINE CORRECT- | | IONS ON REVISION SHEET AND MAKE NECESS- | | ARY CHANGES. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|