2002-09-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUP SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT. 909.1 - THE LAUNDRY TRAY
 SHALL NOT DRAIN THROUGH THE BATHROOM
 GROUP.
 2) SANITARY RISER SHALL REFLECT THE
 FLOOR PLAN. PLEASE SEE RED LINE CORRECT-
 IONS ON REVISION SHEET AND MAKE NECESS-
 ARY CHANGES.
  