Plan Review Notes
Plan Review Notes For Permit 02011150
Permit Number 02011150
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-03 00:00:00PLUMBING PLAN REVIEW,FBC 2001, DENIED
 (1) GENERAL NOTES (14) DESIGN IS NOT BY
 WPB SWIMMING POOL CODE, SEE FBC 2001".
 SEC 424.2.6
 (2) SEC 424.2.6.6.2 SUCTION FITTINGS,
 CLEANING LINE.
 (3) SEC 424..2.7.2 SHOW A DETAIL OF MOUN
 TING AND ANCHORING POOL,SPA EQUIPMENT.
 (4) 424.2.9 WATER SUPPLY,LOCAL ORDINANCE
 #2853-95 BACK FLOW PREVENTER REQUIRED ON
 WATER SERVICE.
 (5) SEC 424.2.13.2 JOINTS, CONNECTIONS,
 PURPLE PRIMER REQUIRED ON PVC PIPING.
 FBC-2001 PLUMBING SEC605.21
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233