Plan Review Notes
Plan Review Notes For Permit 02011029
Permit Number 02011029
Review Stop P
Sequence Number 1
Notes
Date Text
2002-02-03 00:00:00PLUMBING PLAN REVIEW,DENIED.
 (1A) SHT 1 SEPERATE PLANS AND PERMIT FOR
 POOL HEATER (GAS).
 (1B) SHT 1, COMPLY WITH 64E-9.007(14)
 A SKETCH OF THE HEATER INSTALLATION,
 VALVES, PIPE SIZES, MFG. CUT SHTS, MODEL
 BTUS.PRIOR TO INSTALLATION.
 (2)SHT 1 REST RM FACILITIES, COMPLY WITH
 SEC 64E-9.013(3) NUMBER OF FIXTURES REQ.
 BASED ON SQ. FT OF POOL SURFACE(5276SF)
 3 WATER CLOSETS IN WOMEN'S FOR EVERY 2
 IN THE MENS REST RM.(3:2 RATIO)
 (3) SHT 1 COMPLY WITH SEC 64E-9.007(2)
 FILTER EQUIPMENT, MIN OF FOUR TURNOVERS
 OF POOL VOLUME PER DAY.
 END OF COMMENTS PAUL SCHMITZ
 561-659-8096X8233