Plan Review Notes For Permit 02011029 |
Permit Number |
02011029 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-03 00:00:00 | PLUMBING PLAN REVIEW,DENIED. | | (1A) SHT 1 SEPERATE PLANS AND PERMIT FOR | | POOL HEATER (GAS). | | (1B) SHT 1, COMPLY WITH 64E-9.007(14) | | A SKETCH OF THE HEATER INSTALLATION, | | VALVES, PIPE SIZES, MFG. CUT SHTS, MODEL | | BTUS.PRIOR TO INSTALLATION. | | (2)SHT 1 REST RM FACILITIES, COMPLY WITH | | SEC 64E-9.013(3) NUMBER OF FIXTURES REQ. | | BASED ON SQ. FT OF POOL SURFACE(5276SF) | | 3 WATER CLOSETS IN WOMEN'S FOR EVERY 2 | | IN THE MENS REST RM.(3:2 RATIO) | | (3) SHT 1 COMPLY WITH SEC 64E-9.007(2) | | FILTER EQUIPMENT, MIN OF FOUR TURNOVERS | | OF POOL VOLUME PER DAY. | | END OF COMMENTS PAUL SCHMITZ | | 561-659-8096X8233 |
|