Plan Review Notes For Permit 02010811 |
Permit Number |
02010811 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-03-20 00:00:00 | SECOND CHECKLIST: | | 1-NEED RECORDED NOTICE OF COMMENCEMENT. | | 2-DRAWINGS ARE STAMPED FOR IMPACT FEES. | | PLEASE BRING COPY OF PAID RECEIPT. | | 3-DRAWING 5 OF 7 OF PRODUCT APPROVAL FOR | | SLIDING GLASS DOORS IS NOT LEGIBLE. | | -ALSO, PRODUCT APPROVAL IS NOT GOOD FOR | | THE DESIGN PRESSURES CALCULATED BY THE | | PROFESSIONAL ENGINEER OF RECORD. | | SUBMIT PRODUCT APPROVAL THAT MEETS THE | | DESIGN PRESSURES CALCULATED BY THE | | ENGINEER OF RECORD. | | 4-PROVIDE COMPLETE ENERGY CALCULATIONS | | FORM. NOTE: DON'T FORGET TO ASK OWNER/ | | AGENT TO SIGN AND DATE FORM AS WELL. | | SEC. 101.2.2 OF FLORIDA ENERGY | | EFFICIENCY CODE FOR BUILDING | | CONSTRUCTION, 1997 EDITION. | | | | NOTE: | | ADDITIONAL FEES WILL BE CHARGED FOR | | RE-SUBMITTAL FEES. SEE COPY OF RE-SUB | | FORM FOR FEES. |
|