2002-01-31 00:00:00 | CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-TAKE DRAWINGS TO PALM BEACH COUNTY TO |
| VERIFY IF IMPACT FEES ARE DUE OR NOT? |
| BRING BACK STAMPED DRWGS & RECEIPT. |
| 3-ENG'R TO SPECIFY THE DESIGN PRESSURES |
| CALCULATED AT EXTERIOR OPENINGS. |
| SECTION 1606 SBC 1997. |
| 4-PROVIDE PRODUCT APPROVAL AND COMPLETE |
| INFORMATION FOR STORM SHUTTERS. |
| SEE ATTACHED CITY SAMPLE. |
| 5-CONNECTOR SPECIFIED HGA10 IS NOT |
| DESIGNED FOR WOOD STUDS. SEE SIMPSON |
| CATALOGUE AND REVISE AS REQUIRED. |
| 6-SEE PLANS FOR ADDITIONAL COMMENTS. |
| 7-SPECIFY HOW ARE THE TRIPLE OPENING |
| STUDS ATTACHED AT TOP AND BOTTOM. |
| 8-DRAWING 5 OF 7 OF PRODUCT APPROVAL FOR |
| SLIDING GLASS DOORS IS NOT LEGIBLE. |
| PROVIDE LEGIBLE DRAWINGS. |
| -CHECK DESIGN PRESSURES SPECIFIED BY |
| ENGINEER OF RECORD. |
| -PROVIDE 2 COPIES OF PRODUCT APPROVALS. |
| 9-DESIGN CERTIFICATION FOR BUILDING CODE |
| COMPLIANCE FORM IS FOR PALM BEACH CTY |
| NOT FOR CITY OF W.P.B. |
| NOTE: THIS FORM IS NOT REQUIRED TO BE |
| FILED SEPARATELY. SUCH INFORMATION |
| SHALL BE INCLUDED IN THE PLANS. |
| 10-DRAWINGS ARE MISSING THE ELECTRICAL |
| INFORMATION FOR REVIEW. |
| -ALSO, PROVIDE INFORMATION FOR A/C |
| REVIEW. |
| 11-PROVIDE COMPLETE ENERGY CALCULATIONS |
| FORM. |