Plan Review Notes
Plan Review Notes For Permit 02010811
Permit Number 02010811
Review Stop B
Sequence Number 1
Notes
Date Text
2002-01-31 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-TAKE DRAWINGS TO PALM BEACH COUNTY TO
 VERIFY IF IMPACT FEES ARE DUE OR NOT?
 BRING BACK STAMPED DRWGS & RECEIPT.
 3-ENG'R TO SPECIFY THE DESIGN PRESSURES
 CALCULATED AT EXTERIOR OPENINGS.
 SECTION 1606 SBC 1997.
 4-PROVIDE PRODUCT APPROVAL AND COMPLETE
 INFORMATION FOR STORM SHUTTERS.
 SEE ATTACHED CITY SAMPLE.
 5-CONNECTOR SPECIFIED HGA10 IS NOT
 DESIGNED FOR WOOD STUDS. SEE SIMPSON
 CATALOGUE AND REVISE AS REQUIRED.
 6-SEE PLANS FOR ADDITIONAL COMMENTS.
 7-SPECIFY HOW ARE THE TRIPLE OPENING
 STUDS ATTACHED AT TOP AND BOTTOM.
 8-DRAWING 5 OF 7 OF PRODUCT APPROVAL FOR
 SLIDING GLASS DOORS IS NOT LEGIBLE.
 PROVIDE LEGIBLE DRAWINGS.
 -CHECK DESIGN PRESSURES SPECIFIED BY
 ENGINEER OF RECORD.
 -PROVIDE 2 COPIES OF PRODUCT APPROVALS.
 9-DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM IS FOR PALM BEACH CTY
 NOT FOR CITY OF W.P.B.
 NOTE: THIS FORM IS NOT REQUIRED TO BE
 FILED SEPARATELY. SUCH INFORMATION
 SHALL BE INCLUDED IN THE PLANS.
 10-DRAWINGS ARE MISSING THE ELECTRICAL
 INFORMATION FOR REVIEW.
 -ALSO, PROVIDE INFORMATION FOR A/C
 REVIEW.
 11-PROVIDE COMPLETE ENERGY CALCULATIONS
 FORM.