2002-02-14 00:00:00************BUILDING PROVISO************
  
 1) THERE IS A DISCREPANCY AS TO THE TYPE
 OF COLUMN FOR THE OPTIONAL COVERED
 PORCH INDICATED ON SHEET O1L. SECTION A
 STATES 3-1/2"X 3-1/2"X 1/4" STRUCTURAL
 ALUMINUM COLUMN AND DETAIL B STATES 3"X
 3"X 1/4" STEEL COLUMN. PLEASE SUBMIT AN
 ENGINEERED SHOP DRAWING OF THE COLUMN
 THAT IS USED. PLEASE CORRECT THIS ON THE
 PLANS FOR FUTURE SUBMITTALS.
  
 2)FOR FUTURE SUBMITTALS, PLEASE INDICATE
 ON THE COVERED PORCH SECTION ON SHEET
 O1L THAT THE METAL LATH IS REQUIRED TO
 BE ATTACHED WITH NAILS OR STAPLES THAT
 PROVIDE AT LEAST 1-3/4" PENETRATION INTO
 HORIZONTAL WOOD FRAMING MEMBERS PER
 ASTM C-1063.