Plan Review Notes For Permit 02010645 |
Permit Number |
02010645 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-03-08 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) SANITARY RISER DIAGRAM DOES NOT REF- | | LECT FLOOR PLAN, AND DOES NOT MEET CODE | | REQUIREMENTS. | | 2) RISER DIAGRAM SHALL REFLECT HOW PIP- | | ING IS INSTALLED. WASHING MACHINE SHALL | | BE PIPED FIRST, THEN MASTER BATHROOM | | SECOND, BATH 2 NEXT, AND THEN KITCHEN | | LAST. | | 3) WASHING MACHINE TRAP SHALL BE LOW ON | | RISER WITH CLEAN OUT AT 4' ABOVE FLOOR. | | 4) TUB FOR MASTER BATH NOT VENTED. | | 5) TUB FOR BATH #2 NOT VENTED PROPERLY. | | 6) PLEASE SUBMIT A SANITARY RISER DIA- | | GRAM THAT REFLECTS THE FLOOR PLAN AND | | MEETS THE SPC-94. | | | | REVIEW BY KEN STEVENS |
|