Plan Review Notes
Plan Review Notes For Permit 02010645
Permit Number 02010645
Review Stop P
Sequence Number 2
Notes
Date Text
2002-03-08 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SANITARY RISER DIAGRAM DOES NOT REF-
 LECT FLOOR PLAN, AND DOES NOT MEET CODE
 REQUIREMENTS.
 2) RISER DIAGRAM SHALL REFLECT HOW PIP-
 ING IS INSTALLED. WASHING MACHINE SHALL
 BE PIPED FIRST, THEN MASTER BATHROOM
 SECOND, BATH 2 NEXT, AND THEN KITCHEN
 LAST.
 3) WASHING MACHINE TRAP SHALL BE LOW ON
 RISER WITH CLEAN OUT AT 4' ABOVE FLOOR.
 4) TUB FOR MASTER BATH NOT VENTED.
 5) TUB FOR BATH #2 NOT VENTED PROPERLY.
 6) PLEASE SUBMIT A SANITARY RISER DIA-
 GRAM THAT REFLECTS THE FLOOR PLAN AND
 MEETS THE SPC-94.
  
 REVIEW BY KEN STEVENS