 MECHANICAL PERMIT 02010352
  
 AS PER THE FLORIDA ENERGY CODE
 407.1.ABCD.3.3, THE CONDENSING COIL
 SHALL NOT BE INSTALLED IN THE COOL AIR
 STREAM OF ANOTHER AIR CONDITIONING UNIT.
  
 APPLIANCES LISTED FOR OUTDOOR
 INSTALLATIONS SHALL NOT BE INSTALLED
 INSIDE A BUILDING AS PER 1997 SMC
 304.2.2.
  
  