2002-03-05 00:00:00 | *************BUILDING DENIED************ |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) FORM 600A-97 HAS THE WRONG ADDRESS |
| AND IS REQUIRED TO BE SIGNED AND DATED |
| BY THE OWNER/AGENT. PLEASE CORRECT. |
| |
| 3) PLEASE CORRECT THE DESIGN DATA ON |
| SHEET A-1 TO REFER TO THE 1997 STANDARD |
| BUILDING CODE. |
| |
| 4)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - STRUCTURAL WINDOW MULLIONS |
| - EXTERIOR DOORS |
| |
| 5) THE SITE SPECIFIC PRODUCT APPROVAL |
| SUBMITTAL FORM FOR THE NORANDEX SINGLE- |
| HUNG WINDOWS IS REQUIRED TO BE SEALED |
| AND DATED BY THE ENGINEER CERTIFYING THE |
| PRODUCT. THE ARCHITECT IS REQUIRED TO |
| INDICATE DATE IN ADDITION TO SIGNING AND |
| SEALING THE FORM. |
| |
| 6) THE BEDROOM WINDOWS MUST PROVIDE A |
| MINIMUM NET CLEAR OPENING HEIGHT OF 24" |
| TO COMPLY WITH 1997 SBC 1005.4. THE |
| SH 24 WINDOWS TYPICALLY DO NOT PROVIDE |
| THIS. PLEASE PROVIDE CUT SHEETS FROM THE |
| WINDOW MANUFACTURER WHICH INDICATE THAT |
| THE OPENING REQUIREMENTS WILL BE MET. |
| |
| IF YOU HAVE ANY QUESTIONS PLEASE CALL: |