Plan Review Notes
Plan Review Notes For Permit 02010610
Permit Number 02010610
Review Stop R
Sequence Number 2
Notes
Date Text
2002-03-05 00:00:00*************BUILDING DENIED************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FORM 600A-97 HAS THE WRONG ADDRESS
 AND IS REQUIRED TO BE SIGNED AND DATED
 BY THE OWNER/AGENT. PLEASE CORRECT.
  
 3) PLEASE CORRECT THE DESIGN DATA ON
 SHEET A-1 TO REFER TO THE 1997 STANDARD
 BUILDING CODE.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL WINDOW MULLIONS
 - EXTERIOR DOORS
  
 5) THE SITE SPECIFIC PRODUCT APPROVAL
 SUBMITTAL FORM FOR THE NORANDEX SINGLE-
 HUNG WINDOWS IS REQUIRED TO BE SEALED
 AND DATED BY THE ENGINEER CERTIFYING THE
 PRODUCT. THE ARCHITECT IS REQUIRED TO
 INDICATE DATE IN ADDITION TO SIGNING AND
 SEALING THE FORM.
  
 6) THE BEDROOM WINDOWS MUST PROVIDE A
 MINIMUM NET CLEAR OPENING HEIGHT OF 24"
 TO COMPLY WITH 1997 SBC 1005.4. THE
 SH 24 WINDOWS TYPICALLY DO NOT PROVIDE
 THIS. PLEASE PROVIDE CUT SHEETS FROM THE
 WINDOW MANUFACTURER WHICH INDICATE THAT
 THE OPENING REQUIREMENTS WILL BE MET.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202