Plan Review Notes
Plan Review Notes For Permit 02010610
Permit Number 02010610
Review Stop E
Sequence Number 1
Notes
Date Text
2002-01-30 00:00:00*****************UNSAT!*****************
 1) BEDROOM #1 RECETACLE SPACING PER
 210-52(A).
  
 2) SMOKE DETECTORS PER NFPA-72 2-5.2.1.6
  
 3) LOCATION OF A/C CONDENSOR AND GFI ?
  
 PLEASE REVISE FOR ABOVE AND RESUBMIT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 (561) 659-8096 EXT.8392