Plan Review Notes
Plan Review Notes For Permit 02010568
Permit Number 02010568
Review Stop E
Sequence Number 2
Notes
Date Text
2002-01-29 00:00:00********************* UNSAT ************
  
 PLEASE NOTE THAT NOT ALL NOTES FROM
 FIRST REVIEW WERE ADDRESSED.
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS WERE
 SUBMITTED FOR APT PANELS BUT NOTHING FOR
 SERVICE MAIN DISCONNECTS OR APT MAIN
 DISCONNECTS? MAIN DISCONNECTS WOULD BE
 THE FIRST POINT OF ENTRANCE. PLEASE
 SEE 110-9.
  
 2)NOTE: PLEASE NOTE, MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN 100A MAINS
 AND PANELS, CLARIFY METHOD OF GROUNDING
 OR SIZE PER 250-122.
  
 3)NOTE: PLEASE NOTE MISSING TWO OUTLETS
 FOR 2' OF WALL IN APTS #2,#1, CAN BE
 REDLINED ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372