Plan Review Notes
Plan Review Notes For Permit 02010568
Permit Number 02010568
Review Stop E
Sequence Number 1
Notes
Date Text
2002-01-14 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT A TYPICAL
 ELECTRICAL RISER DIAGRAM IS SHOWN ON A3
 AND A DIFFERENT RISER IS SHOWN ON A5
 PLEASE NOTE THAT A COMPLETE RISER
 DIAGRAM IS NEEDED FOR REVIEW. PLEASE
 NOTE GROUPING OF MAIN DISCONNECTS PER
 230-72.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3)NOTE: PLEASE NOTE THAT NO PANEL
 SCHEDULES WERE SUBMITTED FOR UNITS,
 CAN BE
 TYPICAL.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 6)NOTE: PLEASE NOTE THAT NO HANDWRITTEN
 CHANGES MAY BE ON PLANS UNLESS DONE BY
 THE ARCH/ENGINEER OF RECORD AND THEN
 EACH INDIVIDUAL CHANGE MUST BE SIGNED
 AND DATED.471.025/481.221
  
 7)NOTE: PLEASE NOTE/CLARIFY IF THERE
 IS A 2HR SEPARATION OF UNITS IN ORDER
 TO HAVE THE SEPARATE SERVICES THAT ARE
 SHOWN? 230-2
  
 8)NOTE: PLEASE CLARIFY "DOOR" SHOWN IN-
 -FRONT OF STAIRS?
  
 9)NOTE: PLEASE NOTE LOAD CALCULATIONS
 SHOW UNITS 1,2,4,5 AND THEN UNITS 4&6,
 PLEASE CLARIFY 2-#4 UNITS? IS THE UPPER
 #4 SUPPOSE TO BE #3
  
 10)NOTE: PLEASE ELECTRICAL PLANS DUE TO
 NOTES ON SIDE OF PLANS.
  
  
 PLEASE MAKE THE ABOVE CORRECTIONS, AND
 SUBMIT FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved