Plan Review Notes
Plan Review Notes For Permit 02010464
Permit Number 02010464
Review Stop M
Sequence Number 1
Notes
Date Text
2002-01-11 00:00:00*******************DENIED***************
  
  
 EXHAUST DUCT SHALL BE A MINIMUM OF 10
 FTFROM ANY ADJACENT BUILDING, PARKING
 AREA, ADJACENT PROPERTY LINE, WINDOW,
 OR DOOR.1997 SMC 506.1 & NFPA 96
 4-8.2.1 (A).
  
 PLEASE INDICATE HEIGHT OF EXHAUST DUCT.
 CLARIFY HOW ACCESS FOR MAINTENANCE AND
 CLEANING WILL BE OBTAINED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.