Plan Review Notes For Permit 02010378 |
Permit Number |
02010378 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-02-04 00:00:00 | | | PROVISO: | | | | PLAN SHEET A-1 INDICATES AN EXISTING 1 | | HOUR RATED WALL.NO PENETRATIONS ARE | | SHOWN ON PLAN.PLEASE NOTE ANY | | PENETRATIONS THROUGH A WALL OR | | PARTITION HAVING A FIRE RESISTANCE | | RATING OF 1 OR MORE HOURS SHALL BE | | PROTETED BY A FIRE DAMPER. | | (1997 SMC 610.1.2) | | | | SPECIFIC LOCATION OF EACH FIRE DAMPER | | SHALL BE PROPERLY IDENTIFIED ON THE | | BUILDING PLAN.(1997 SMC 610.6) | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|