Plan Review Notes For Permit 02010378 |
Permit Number |
02010378 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-01-29 00:00:00 | BUILDING PLAN REVIEW | | ******PROVISO******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | SBC = STANDARD BUILDING CODE 1997 | | SBC*= STANDARD BUILD'G CODE (CITY AMEND) | | | | --PROVISO-- | | COMMENT NO.2 OF FIRE DEPARTMENT REVIEW, | | DATED 1/25/02, REGARDING DOOR SWING | | ACROSS CORRIDOR MUST BE ADDRESSED. | | | | --PROVISO-- | | SBC 1004.2.1 THE TWO EXITS FROM "OTHER | | SUITES" ARE TOO CLOSE TOGETHER TO BE | | CONSIDERED "...TWO INDEPENDENT EXITS". | | THIS IS ACCEPTABLE ONLY, UNDER THE | | EXCEPTION GIVEN IN SBC 1020.1 'SINGLE | | EXIT', IF NO MORE THAN 40 PERSONS OCCUPY | | THAT SPACE. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|