2002-01-17 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC* 104.2.3NONE OF THE SUBMITTED
 PLANS HAVE BEEN SEALED PROPERLY.
  
 3) SBC 1004.2.1EACH TENANT AREA SHALL
 HAVE ACCESS TO TWO INDEPENDENT EXITS.
 SHOW ENTRANCES/EXITS FROM THE AREA
 DESCRIBED AS "OTHER SUITES", AS THE
 PLANS ARE SHOWING ONE DOOR FILLED-IN.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499