Plan Review Notes
Plan Review Notes For Permit 02010255
Permit Number 02010255
Review Stop E
Sequence Number 1
Notes
Date Text
2002-01-08 00:00:00****************UNSAT!******************
  
  
 PLEASE PROVIDE THE FOLLOWING AND RESUBM
 IT FOR REVIEW:
  
 1)COMPLETE THE AIC RATING TO THELIN SIDE
 OF THE MAIN DISCONNECTING MEANS.
 2)PROVIDE LOAD CALCULATION FOR THE SERVI
 CE.
 3)INCLUDE THE CONDUIT SIZE AND TYPE BETW
 EEN THE DISCONNECTS.
 4)INDICATE THE WIRE SIZE FEEDING THE DIS
 CONNECT.
 5)INDICATE YYPE AND LOCATION OF PANELS.
 6)PLEASE SHOW SIZE OF GROUNDING ELECTROD
 E CONDUCTOR.
  
 BILL TROBAUGH
 ELECTRICAL PLAN EXAMINER
 (561)0659-8096 EXT.8392