Plan Review Notes For Permit 02010252 |
Permit Number |
02010252 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-01-08 00:00:00 | *****************UNSAT!***************** | | | | 1)SEE NOTES ON RISER DIAGRAM. | | 2)PROVIDE AIC RATING TO THE LINE SIDE OF | | DISCONNECTING MEANS. | | 3)PROVIDE DRAWINGS FOR ALL UNITS.PLEASE | | MAKE PLANS MORE LEGIBLE. | | 4)SHOW SMOKE DETECTORS IN ALL UNITS. | | 5)LIGHTING AS PER 210-70 | | 6)PROVIDE PANEL SCHEDULES FOR ALL UNITS. | | 7)GFI OUTLETS PER 210-52E. | | 8)BEDROOM OUTLETS PER 210-12(ARC FAULT). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | (561) 659-8096 EXT.8392 |
|