2002-01-08 00:00:00*****************UNSAT!*****************
  
 1)SEE NOTES ON RISER DIAGRAM.
 2)PROVIDE AIC RATING TO THE LINE SIDE OF
 DISCONNECTING MEANS.
 3)PROVIDE DRAWINGS FOR ALL UNITS.PLEASE
 MAKE PLANS MORE LEGIBLE.
 4)SHOW SMOKE DETECTORS IN ALL UNITS.
 5)LIGHTING AS PER 210-70
 6)PROVIDE PANEL SCHEDULES FOR ALL UNITS.
 7)GFI OUTLETS PER 210-52E.
 8)BEDROOM OUTLETS PER 210-12(ARC FAULT).
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.