Plan Review Notes
Plan Review Notes For Permit 02010168
Permit Number 02010168
Review Stop B
Sequence Number 2
Notes
Date Text
2002-03-19 00:00:00***TRUSS ENGINEERING***
 C-B-A-B-C
  
 REVIEWED UNDER :
 1997 STANDARD BUILDING CODE
  
 1)- FG-5 A5 INDICATES A 3 POINT BEARING
 GIRDER TRUSS, TRUSS ENG. INDICATES A
 5 POINT BEARING, MISSING BEARING POINTS
 13 & 14.
  
 2)- SG-1 TRUSS ENG. POINT #5 INDICATES
 2060 LBS. UPLIFT WHERE AS SH A5 NOTE
 A-3 INDICATES 1370 OR 1890, SHORT
 RESTRAINT OR UPLIFT VALUE.
  
 3)- TRUSS ENG H-4 TRUSS ENG POINT #1 IN-
 DICATES 3203 LBS UPLIFT, POINT 11 INDICA
 TES 3174, ARCH A-6 DETAIL 4/10 IS A WALL
 SECTION TO A FLOOR GIRDER TRUSS CONNEC-
 TION MISSING INFO FOR THE ROOF GIRDER TO
 2ND STORY WALL CONNECTION?
  
 4)- TRUSS ENG H-5,- H-8,& T-1 INDICATE A
 3" BEARING END (BUCKET) ARCH SHEET A6
 INDICATES A (WA-5) NOT IN SCHEDULE?
  
 5)- WHERE MULTIPLE STRAPS ARE TO BE USED
 IN CMU OR CONCRETE A DERATING SHALL BE
 REQUIRED WHEN THEY ARE CLOSER THAN 8".
 USP SHALL CALCULATE THE AMOUNT OF DERAT-
 ING REQUIRED.
  
 6)- SHEET A-6 DETAIL 2 INDICATES A STRAP
 TO BE WELDED TO A MANUFACTURED BUCKET.
 SHALL REQUIRE MANUFACTURES APPROVAL &
 FIELD WELDING REQUIRES CERTIFICATION
 OF THE WELDER.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412