Plan Review Notes
Plan Review Notes For Permit 02010047
Permit Number 02010047
Review Stop P
Sequence Number 1
Notes
Date Text
2002-01-18 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A2.0, 1 DRINKING FOUNTAIN REQUIR-
 ED PER SPC TABLE 407. HI-LOW TO COMPLY
 WITH FACBC 4.1.3(10) TO PROVIDE FOR
 THOSE WITH DIFFICULTY BENDING OR STOOP-
 ING. ALSO COMPLY WITH FACBC 4.15, 4.15.2
 & 4.15.5
  
 2) SHT A2.O/A4.0 WATER CLOSETS, SHOW
 COMPLIANCE WITH 4.16, 4.14.2, 4.16.5 -
 (MENS ROOM #103), SHOW W/C'S 1'6" OFF
 WALL.
  
 3) SHT A2.0/A4.0 URNAL, SHOW COMPLIANCE
 WITH 4.18, 4.18.3.
  
 4) SHT A2.0/A4.0 LAVS, SHOW COMPLIANCE
 WITH 4.19, 4.19.3, 4.19.4 & 4.19.5
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377