2002-01-11 00:00:00 | ********************DENIED************** |
| |
| 1.PLAN SHEET M1.1 INDICATE AIR FROM |
| THE MALE AND FEMALE BATHROOMS IS |
| TO BE TRANSFERED INTO THE COMMON |
| AREAS, AS PER 1997 SMC 503.3.1 - |
| AIR EXHAUSTED FROM BATH TOILET, |
| URINAL, LAVATORY, LOCKER, COAT ROOM |
| OR SIMILAR ROOMS SHALL NOT BE |
| RECIRCULATED. |
| |
| 2.PLEASE NOTE FIRE DEPARTMENT COMMENT |
| #1,SHOULD THESE ROOMS HAVE A FIRE |
| SEPARATION, FIRE DAMPERS WILL BE |
| REQUIRED.INDICATE LOCATION OF |
| FIRE DAMPERS AND INSTALLATION DETAIL |
| ON PLAN. |
| |
| 3.WHAT IS THE UTILITY ROOM USED FOR? |
| |
| 4.AS PER 1997 SMC 406.1, FAN SHUTDOWN |
| BY DUCT SMOKE DETECTOR IN THE RETURN |
| AIRSTREAM PROIR TO ANY EXHAUSTING |
| FROM THE BUILDING OR MIXING WITH |
| FRESH AIR MAKEUP. |
| |
| 5.FAN SHUTDOWN BY DUCT SMOKE DETECTOR |
| WITH NOTIFICATION TO ALARM/STROBE IN |
| NORMALLY OCCUPIED AREAS. NFPA 90A |
| 4-4.4.3. |
| |
| 6.PLEASE INDICATE SIZE AND TERMINATION |
| OF THE CONDENSATE.UNITS LARGER |
| THAN 3 TON SHALL TERMINATE INTO: |
| |
| 1.AN APPROVED DRY WELL |
| 2.TO STORM DRAIN |
| |