Plan Review Notes
Plan Review Notes For Permit 02010047
Permit Number 02010047
Review Stop M
Sequence Number 1
Notes
Date Text
2002-01-11 00:00:00********************DENIED**************
  
 1.PLAN SHEET M1.1 INDICATE AIR FROM
 THE MALE AND FEMALE BATHROOMS IS
 TO BE TRANSFERED INTO THE COMMON
 AREAS, AS PER 1997 SMC 503.3.1 -
 AIR EXHAUSTED FROM BATH TOILET,
 URINAL, LAVATORY, LOCKER, COAT ROOM
 OR SIMILAR ROOMS SHALL NOT BE
 RECIRCULATED.
  
 2.PLEASE NOTE FIRE DEPARTMENT COMMENT
 #1,SHOULD THESE ROOMS HAVE A FIRE
 SEPARATION, FIRE DAMPERS WILL BE
 REQUIRED.INDICATE LOCATION OF
 FIRE DAMPERS AND INSTALLATION DETAIL
 ON PLAN.
  
 3.WHAT IS THE UTILITY ROOM USED FOR?
  
 4.AS PER 1997 SMC 406.1, FAN SHUTDOWN
 BY DUCT SMOKE DETECTOR IN THE RETURN
 AIRSTREAM PROIR TO ANY EXHAUSTING
 FROM THE BUILDING OR MIXING WITH
 FRESH AIR MAKEUP.
  
 5.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS. NFPA 90A
 4-4.4.3.
  
 6.PLEASE INDICATE SIZE AND TERMINATION
 OF THE CONDENSATE.UNITS LARGER
 THAN 3 TON SHALL TERMINATE INTO:
  
 1.AN APPROVED DRY WELL
 2.TO STORM DRAIN
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.