Plan Review Notes
Plan Review Notes For Permit 02010047
Permit Number 02010047
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-01-03 00:00:00 
  
  
  
 1) SINCE NO FIRE SPRINKLERS ARE PLANNED
 THE ELECTRICAL ROOM, MECHANICAL, AND
 UTILITY ROOMS ARE TO BE AT LEAST ONE
 HOUR FIRE SEPARATED WITH C LABELED FIRE
 DOORS WITH CLOSERS.
 2) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION FOR THE WALLS AND CEILINGS.
 3) BUILDING ADDRESS IS REQUIRED PER
 CITY CODE 3343-00.
  