Plan Review Notes For Permit 02010047 |
Permit Number |
02010047 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-01-03 00:00:00 | | | | | | | | | 1) SINCE NO FIRE SPRINKLERS ARE PLANNED | | THE ELECTRICAL ROOM, MECHANICAL, AND | | UTILITY ROOMS ARE TO BE AT LEAST ONE | | HOUR FIRE SEPARATED WITH C LABELED FIRE | | DOORS WITH CLOSERS. | | 2) PLEASE PROVIDE INTERIOR FINISH | | INFORMATION FOR THE WALLS AND CEILINGS. | | 3) BUILDING ADDRESS IS REQUIRED PER | | CITY CODE 3343-00. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|