Plan Review Notes
Plan Review Notes For Permit 02010047
Permit Number 02010047
Review Stop B
Sequence Number 1
Notes
Date Text
2002-01-16 00:00:00PLEASE PROVIDE A RECENT PROPERTY SURVEY
 AND A SITE PLAN WITH DIMENSIONS LOCATING
 THE PROPOSED BUILDING ON THE PROPERTY.
 INCLUDE TOPOGRAPHIC INFORMATION SO
 THATCOMPLIANCE WITH HANDICAP SITE
 ACCESSIBILTY MAY BE DETERMINED.
  
 PROVIDE PRODUCT TEST REPORTS AND OR
 NOTICE OF ACCEPTANCE DATA FOR THE
 DOORS, WINDOWS AND ROOF COVERING TO BE
 USED.
  
 SHOW THE METHOD OF HURRICANE MISSILE
 IMPACT RESISTANT FOR THE EXTERIOR
 GLAZED PORTIONS OF THE BUILDING.
  
 SHOW THE SPECIFIC CODE AND DESIGNS
 STANDARDS USED FOR THIS BUILDING.
  
 THE ROOF NOTES ON SHEET S3 DO NOT
 DEFINETHE SIZE OR LOCATION OF THE 3
 ZONES FOR WIND PRESSURE.INCLUDE THE
 PRESSURE ZONES FOR COMPONENTS AND
 CLADDING ON THE WALLS ALSO.
  
 PLEASE PROVIDE STRUCTURAL CALCULATIONS
 FOR THE 2X4 PURLINS ON THE ROOF
 DEMONSTRATING THEIR ABILITY TO RESIST
 UPLIFT THE DECLARED UPLIFT PRESSURES.