Plan Review Notes
Plan Review Notes For Permit 02010043
Permit Number 02010043
Review Stop P
Sequence Number 1
Notes
Date Text
2002-01-18 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT P1.2 WATER HEATER DETAIL. RELIEF
 LINE AND PAN DRAIN TO BE PIPED SEPARATE
 TO FLOOR SINK. SPC SEC 507.8.4 - 1" FOR
 PAN DRAIN (SEC 507.8.2), FULL SIZE FOR
 RELIEF LINE.
  
 2) SHT P1.2 WATER HEATER DETAIL/SANITARY
 RISER DIAGRAM. FUNNEL FLOOR DRAIN NOT
 APPROVED, ALL INDIRECT WASTE TO FLOOR
 SINK. SPC SEC 804.5.
  
 3) SHT P1. WATER RISER DIAGRAM. AIR
 CHAMBERS SHOWN. PLEASE SHOW WATER HAMMER
 ARRESTORS, (NOTE #10), NEAR FIXTURES NOT
 ON TOP OF DROP. LOCATE ACCORDING TO PDI-
 WH 201 AND MANUFACTURES INSTALLATION IN-
 STRUCTIONS, IN AN "EFFECTIVE RANGE".
 SHOW DETAILS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377