Plan Review Notes For Permit 02010043 |
Permit Number |
02010043 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-01-18 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) SHT P1.2 WATER HEATER DETAIL. RELIEF | | LINE AND PAN DRAIN TO BE PIPED SEPARATE | | TO FLOOR SINK. SPC SEC 507.8.4 - 1" FOR | | PAN DRAIN (SEC 507.8.2), FULL SIZE FOR | | RELIEF LINE. | | | | 2) SHT P1.2 WATER HEATER DETAIL/SANITARY | | RISER DIAGRAM. FUNNEL FLOOR DRAIN NOT | | APPROVED, ALL INDIRECT WASTE TO FLOOR | | SINK. SPC SEC 804.5. | | | | 3) SHT P1. WATER RISER DIAGRAM. AIR | | CHAMBERS SHOWN. PLEASE SHOW WATER HAMMER | | ARRESTORS, (NOTE #10), NEAR FIXTURES NOT | | ON TOP OF DROP. LOCATE ACCORDING TO PDI- | | WH 201 AND MANUFACTURES INSTALLATION IN- | | STRUCTIONS, IN AN "EFFECTIVE RANGE". | | SHOW DETAILS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|