Plan Review Notes For Permit 02010043 |
Permit Number |
02010043 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-01-08 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE NOTES FOR ELECTRICAL | | RISER. | | PLEASE NOTE #1 SHOWS AN EQUIPMENT GRND | | BEING INSTALLED TO PANEL "A", PLEASE | | CLARIFY IF THIS FEED IS COIMING FROM | | FPL OR OTHER SERVICE MEANS? | | IF FROM FPL, NO EQUIPMENT GROUNDING | | UNTIL AFTER FIRST MEANS OF DISCONNETC. | | THIS IS PARALELLING THE NEUTRAL. | | | | 2)NOTE: PLEASE NOTE THAT THE GROUNDING | | ELECTRODE CONDUCTOR IS BEING SHOWN AS | | #4, PLEASE SEE 250-66 FOR SERVICE | | ENTRANCE CONDUCTOR SIZE. | | | | 3)NOTE: PLEASE CHECK WITH FIRE REVIEW, | | LIGHTING IN BATHS SHOWING NOTE THAT TIME | | "ON" IS ONLY FROM 9AM-6AM. PLEASE NOTE | | LIFE SAFETY ISSUES AND IF THERE MIGHT BE | | ANY CLEANING PERSONNEL IN AFTER THE | | NORMAL OPERATING HOURS? PLEASE CALL | | MIKE CARSILLO AT EXT 8497 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|