Plan Review Notes
Plan Review Notes For Permit 02010043
Permit Number 02010043
Review Stop E
Sequence Number 1
Notes
Date Text
2002-01-08 00:00:00****************** UNSAT ***************
  
  
 1)NOTE: PLEASE SEE NOTES FOR ELECTRICAL
 RISER.
 PLEASE NOTE #1 SHOWS AN EQUIPMENT GRND
 BEING INSTALLED TO PANEL "A", PLEASE
 CLARIFY IF THIS FEED IS COIMING FROM
 FPL OR OTHER SERVICE MEANS?
 IF FROM FPL, NO EQUIPMENT GROUNDING
 UNTIL AFTER FIRST MEANS OF DISCONNETC.
 THIS IS PARALELLING THE NEUTRAL.
  
 2)NOTE: PLEASE NOTE THAT THE GROUNDING
 ELECTRODE CONDUCTOR IS BEING SHOWN AS
 #4, PLEASE SEE 250-66 FOR SERVICE
 ENTRANCE CONDUCTOR SIZE.
  
 3)NOTE: PLEASE CHECK WITH FIRE REVIEW,
 LIGHTING IN BATHS SHOWING NOTE THAT TIME
 "ON" IS ONLY FROM 9AM-6AM. PLEASE NOTE
 LIFE SAFETY ISSUES AND IF THERE MIGHT BE
 ANY CLEANING PERSONNEL IN AFTER THE
 NORMAL OPERATING HOURS? PLEASE CALL
 MIKE CARSILLO AT EXT 8497
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372