2002-01-31 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FL ENERGY CODE 103.1.2BEFORE A
 BUILDING PERMIT CAN BE ISSUED, THE
 SUBMITTED ENERGY CODE COMPLIANCE FORMS
 SHALL BE SIGNED BY THE BUILDING OWNER,
 THE OWNER'S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY
 THE OWNER.
  
 4) SBC* 104.1.1A SEPARATE ROOFING
 PERMIT APPLICATION IS REQUIRED.
  
 5) ROOF TRUSS DRAWINGS SHALL BE
 SUBMITTED.
  
 6) SBC* 104.2.2PREFABRICATED ROYALL
 WALL PANELS.ENGINEERING DETAILS,
 INCLUDING ANCHORAGE TO THE FOUNDATIONS,
 SIGNED AND SEALED BY THE ENGINEER, SHALL
 BE SUBMITTED.ASSOCIATED WINDOW/DOOR
 HEADER AND FASTENING DETAILS ARE ALSO
 REQUIRED.
  
 7) SBC TABLE 600THE "LEFT ELEVATION"
 (EAST ELEVATION) SETBACK IS 8'6".FOR
 TYPE V CONSTRUCTION AND A SETBACK
 BETWEEN 3' AND 10', TABLE 600 ALLOWS FOR
 10% OF THE WALL AREA TO BE UNPROTECTED
 OPENINGS.THE PROPOSED AREA OF WINDOWS
 IN THIS WALL EXCEEDS THE ALLOWABLE
 PERCENTAGE.ADJUST THE SETBACK TO AT
 LEAST 10' OR AMEND THE WINDOW AREA TO
 COMPLY.
  
 8) SBC 1804.1.3THE PLANS SHALL BE
 AMENDED TO SHOW THE BASE LEVEL FOR THE
 EXTERIOR WALL FOUNDATIONS AT LEAST 12"
 BELOW FINISH GRADE.
  
 9) SBC* 1606.4THE PLANS SHALL MAKE
 REFERENCE TO THE REQUIREMENT FOR STORM
 SHUTTERS ON ALL WINDOWS AND DOORS EXCEPT
 THE FRONT ENTRANCE DOOR.
  
 10) SBC 2405.2.1THE GLAZING IN THE
 PATIO DOORS AND THE DOOR TO THE PATIO IS
 IN A "HAZARDOUS LOCATION".PROVIDE
 DETAILS TO SHOW COMPLIANCE WITH THE
 REQUIREMENT FOR 'SAFETY GLASS'.
  
 11) SBC 2309.6THE PLANS SHALL BE
 AMENDED TO SHOW AN INTERIOR ATTIC ACCESS
 OPENING NOT LESS THAN 22"X36".
  
 12) SBC 2309.7ATTIC SPACE VENTILATION
 SHALL BE PROVIDED IN COMPLIANCE WITH THE
 AREA AND LOCATION REQUIREMENTS.
  
 13) TYPICAL HIP TRUSS CONNECTION TO WALL
 THE TYPICAL WALL SECTION SHOWS SIMPSON
 LGT2 CONNECTORS WITH 14-10D NAILS INTO
 THE HIP TRUSS.THIS WOULD RESULT IN
 REDUCED LOAD CAPACITY COMPARED TO THE
 SIMPSON RECOMMENDATION FOR 14-16D
 FASTENERS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499