2002-01-31 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| SBC = STANDARD BUILDING CODE 1997 |
| SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| FL ENERGY CODE = FLORIDA ENERGY |
| EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) FL ENERGY CODE 103.1.2BEFORE A |
| BUILDING PERMIT CAN BE ISSUED, THE |
| SUBMITTED ENERGY CODE COMPLIANCE FORMS |
| SHALL BE SIGNED BY THE BUILDING OWNER, |
| THE OWNER'S ARCHITECT OR OTHER |
| AUTHORIZED AGENT LEGALLY DESIGNATED BY |
| THE OWNER. |
| |
| 4) SBC* 104.1.1A SEPARATE ROOFING |
| PERMIT APPLICATION IS REQUIRED. |
| |
| 5) ROOF TRUSS DRAWINGS SHALL BE |
| SUBMITTED. |
| |
| 6) SBC* 104.2.2PREFABRICATED ROYALL |
| WALL PANELS.ENGINEERING DETAILS, |
| INCLUDING ANCHORAGE TO THE FOUNDATIONS, |
| SIGNED AND SEALED BY THE ENGINEER, SHALL |
| BE SUBMITTED.ASSOCIATED WINDOW/DOOR |
| HEADER AND FASTENING DETAILS ARE ALSO |
| REQUIRED. |
| |
| 7) SBC TABLE 600THE "LEFT ELEVATION" |
| (EAST ELEVATION) SETBACK IS 8'6".FOR |
| TYPE V CONSTRUCTION AND A SETBACK |
| BETWEEN 3' AND 10', TABLE 600 ALLOWS FOR |
| 10% OF THE WALL AREA TO BE UNPROTECTED |
| OPENINGS.THE PROPOSED AREA OF WINDOWS |
| IN THIS WALL EXCEEDS THE ALLOWABLE |
| PERCENTAGE.ADJUST THE SETBACK TO AT |
| LEAST 10' OR AMEND THE WINDOW AREA TO |
| COMPLY. |
| |
| 8) SBC 1804.1.3THE PLANS SHALL BE |
| AMENDED TO SHOW THE BASE LEVEL FOR THE |
| EXTERIOR WALL FOUNDATIONS AT LEAST 12" |
| BELOW FINISH GRADE. |
| |
| 9) SBC* 1606.4THE PLANS SHALL MAKE |
| REFERENCE TO THE REQUIREMENT FOR STORM |
| SHUTTERS ON ALL WINDOWS AND DOORS EXCEPT |
| THE FRONT ENTRANCE DOOR. |
| |
| 10) SBC 2405.2.1THE GLAZING IN THE |
| PATIO DOORS AND THE DOOR TO THE PATIO IS |
| IN A "HAZARDOUS LOCATION".PROVIDE |
| DETAILS TO SHOW COMPLIANCE WITH THE |
| REQUIREMENT FOR 'SAFETY GLASS'. |
| |
| 11) SBC 2309.6THE PLANS SHALL BE |
| AMENDED TO SHOW AN INTERIOR ATTIC ACCESS |
| OPENING NOT LESS THAN 22"X36". |
| |
| 12) SBC 2309.7ATTIC SPACE VENTILATION |
| SHALL BE PROVIDED IN COMPLIANCE WITH THE |
| AREA AND LOCATION REQUIREMENTS. |
| |
| 13) TYPICAL HIP TRUSS CONNECTION TO WALL |
| THE TYPICAL WALL SECTION SHOWS SIMPSON |
| LGT2 CONNECTORS WITH 14-10D NAILS INTO |
| THE HIP TRUSS.THIS WOULD RESULT IN |
| REDUCED LOAD CAPACITY COMPARED TO THE |
| SIMPSON RECOMMENDATION FOR 14-16D |
| FASTENERS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| IF YOU HAVE ANY QUERIES PLEASE CALL: |
| ROBERT BROWN(561) 659 8096 EXT 8499 |