Plan Review Notes For Permit 01121731 |
Permit Number |
01121731 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-03-12 00:00:00 | ************ UNSAT ***************** | | | | 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS, | | FOR ANY EXIT/EM LIGHTING REQ`MENTS. | | | | 2)NOTE: PLEASE CLARIFY WHAT HAPPENED TO | | UPSTAIRS ELECTRICAL? | | | | 3)NOTE: PLEASE NOTE MISSING EQUIPMENT | | GROUNDING CONDCUTOR BETWEEN FIRST MEANS | | OF DISCONNECT AND PANEL. SIZE PER | | 250-122 | | | | 4)NOTE: PLEASE CLARIFY IF USE WILL BE | | GOING BACKTO RESIDENTIAL? PLEASE NOTE | | LOAD CALCUALTIONS ARE SHOWN FOR RES AND | | NOT COMMERCIAL USE? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT8372 |
|